control keypad
vacon • 75
24-hour support: +358-(0)40-8371 150 • Email: [email protected]
7
To change the value: Enter the edit mode by pressing
Menu button right
. The value starts blinking.
Use the
Browser buttons
to change the fan mode and confirm the change with the
enter
button. If
you do not want to change the value, return to the previous level with
Menu button left
. See Figure
7.21 .
Figure
7
-
18. Fan control function
HMI acknowledge timeout (P6.7.3)
This function allows the user to change the timeout of the HMI acknowledgement time. The inverter
waits for the HMI acknowledgment in accordance with the value of this parameter.
Note! If the inverter has been connected to the PC with a normal cable, the default values of
parameters 6.7.3 and 6.7.4 (200 and 5) must not be changed.
If the inverter has been connected to the PC via a modem and there is a delay in transferring
messages, the value of parameter 6.7.3 must be set according to the delay as follows:
Example:
Transfer delay between the inverter and the PC = 600 ms
The value of par. 6.7.3 is set to 1200 ms (2 x 600, sending delay + receiving
delay)
The corresponding setting shall be entered in the
Misc
part of the file
NCDrive.ini:
Retries = 5
AckTimeOut = 1200
TimeOut = 6000
It must also be considered that intervals shorter than the AckTimeOut time
cannot be used in NC-Drive monitoring.
Enter the edit mode by pressing
Menu button right
. The current value starts to blink. Use the
Browser buttons
to change the acknowledgement time. Confirm the change with the
enter
button or
return to the previous level with Menu button left.
READY
I/Oterm
READY
I/Oterm
enter
READY
I/Oterm
Fan control
Continuous
Fan control
Fan control
Continuous
Temperature