![Vacon NXI Series User Manual Download Page 35](http://html1.mh-extra.com/html/vacon/nxi-series/nxi-series_user-manual_847731035.webp)
cabling and connections
vacon • 33
24-hour support: +358-(0)40-8371 150 • Email: [email protected]
6
5
Connect the cables:
Strip the motor and DC supply cables as advised in Figure
6-2 and
Table
6-6.
Remove the screws of the cable protection plate. Do not open the
cover of the power unit!
Make holes into and pass the cables through the rubber grommets
on the bottom of the power unit. The rubber grommets are
delivered in a separate bag.
Connect the DC supply, motor and control cables into their
respective terminals.
For information on the installation of greater units, please contact
the factory or your local distributor.
For Information on cable installation according to UL regulations,
see Chapter
6.1.3.
For information on cable installation according to EMC
regulations, see Chapter
6.1.3.
Make sure that the control cable wires do not come in contact with
the electronic components of the unit.
If an external brake resistor (optional) is used, connect its cable to
the appropriate terminal.
Check the connection of the earth cable to the motor and the
inverter terminals marked with
.
Connect the separate shield of the power cable to the earth
terminals of the inverter, motor and the supply centre.
Attach the cable protection plate with the screws.
Ensure that the control cables or the cables of the unit are not
trapped between the frame and the protection plate.