fault tracking
vacon • 23
24-hour s358 (0)40 837 1150 • Email: [email protected]
8
Note: These Analog Value objects are introduced in BACnet SW version: OPTCJ_10522V009.vcn
1)
FBFixedControlWord PDI 0, bit encoding (
All-in-One Applications
)
B0=RUN;
0=Stop, 1=Run
B1=DIRECTION;
0=Fwd, 1=Rev
B2=FaultRST;
Reset on rising edge
B3-15
Application Specific
2)
FBGeneralControlWord PDI 1, bit encoding
Application Specific
3)
FBFixedStatusWord (MCStatus) PDO 0, bit encoding
B0=Ready;
0=not ready, 1=ready
B1=Run;
0=stopped, 1=running
B2=Direction;
0=clockwise, 1=counterclockwise
B3=Fault;
1=the FC is faulted and stopped (?)
B4=Warning;
1=warning
B5=AtReference;
1=at reference speed
B6=ZeroSpeed;
1=at zero speed
B7=FluxReady;
1=flux ready
B8=TCSpeedLimitActive;
B9=DetectedEncoderDirection;
B10=UVFastStop;
B11=DC brake status 1=DC brake active
B12-15 Firmware Specific
* Not all the bits are supported in every application
4)
FBGeneralStatusWord PDO 1, bit encoding
Application Specific