Pump and fan control with autochange
6 Special parameters, Groups 2—9
6.1 Parameter tables
Group 2, Input signal parameters
Code
Parameter
Range
Step
Default
Custom
Description
Page
2
.
1
DIA2 function
0—10
1
11
0 = Not used
20
(terminal 9)
1 = Ext. fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Acceler./deceler. time selection
5 = Reverse
6 = Jogging frequency
7 = Fault reset
8 = Acc./dec. operation prohibit
9 = DC-braking command
10 = Motor potentiometer UP
11 = Interlock input, autochange 1
2
.
2
DIA3 function
0—10
1
11
0 = Not used
21
(terminal 10)
1 = Ext. fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Acceler./deceler. time selection
5 = Reverse
6 = Jogging frequency
7 = Fault reset
8 = Acc./dec. operation prohibit
9 = DC-braking command
10 = Motor potentiometer DOWN
11 = Interlock input, autochange 2
2
.
3
U
in
signal range
0—2
1
0
0 = 0—10 V
21
1 = Custom setting range
2 = 2—10 V
2
.
4
U
in
custom setting min.
0—100%
0.01%
0.00%
21
2
.
5
U
in
custom setting max.
0—100%
0.01%
100.00%
21
2
.
6
U
in
signal inversion
0—1
1
0
0 = Not inverted
21
1 = Inverted
2
.
7
U
in
signal filter time
0—10s
0.01s
0.1s
0 = No filtering
21
2
.
8
I
in
signal range
0—2
1
1
0 = 0—20 mA
21
1 = 4—20 mA
2 = Custom setting range
2. 9
I
in
custom setting minim.
0—100%
0.01%
0.00%
21
2. 10
I
in
custom setting maxim.
0—100%
0.01% 100.00%
21
2
.
11
I
in
signal inversion
0—1
1
0
0 = Not inverted
22
1 = Inverted
2
.
12
I
in
signal filter time
0 —10s
0.01s
0.1s
0 = No filtering
22
2
.
13
DIB5 function
0—9
1
6
0 = Not used
22
(terminal 15)
1 = Ext. fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Acc./dec. time selection
5 = Reverse
6 = Jogging speed
7 = Fault reset
8 = Acc./dec. operation prohibit
9 = DC-braking command
10 = PI-contr. reference selection
11 = Interlock input, autochange 3
Note!
= Parameter value can be changed only when the frequency converter is stopped