8
vacon • 71
Options
Copying parameters
NOTE:
This feature is available with graphical keypad only.
The parameter copy function can be used to copy parameters from one drive to another.
The parameters are first saved to the keypad, then the keypad is detached and connected to another
drive. Finally the parameters are downloaded to the new drive restoring them from the keypad.
Before any parameters can successfully be copied from one drive to another the drive has to be
stopped when the parameters are downloaded.
•
First go into
User settings
menu and locate the
Parameter backup
submenu. In the
Param-
eter backup
submenu, there are three possible functions to be selected:
•
Restore factory defaults
will re-establish the parameter settings originally made at the fac-
tory.
•
By selecting
Save to keypad
you can copy all parameters to the keypad.
•
Restore from keypad
will copy all parameters from keypad to a drive.
Figure 54. Parameter copy.
NOTE:
If the keypad is changed between drives of different sizes, the copied values of these param-
eters will not be used:
Motor nominal current (P3.1.1.4)
Motor nominal voltage (P3.1.1.1)
Motor nominal speed (P3.1.1.3)
Motor nominal power (P3.1.1.6)
Motor nominal frequency (P3.1.1.2)
Motor cosphi (P3.1.1.5)
Switching frequency (P3.1.2.1)
Motor current limit (P3.1.1.7)
Stall current limit (P3.9.12)
Stall time limit (P3.9.13)
Stall frequency (P3.9.14)
Maximum frequency (P3.3.2)
STOP
READY
Keypad
Application selection
HVAC
User settings
Drive name
Drive
Parameter backup
( 3 )
ID:
M6.5
STOP
READY
Keypad
Restore factory defaults
Parameter backup
Restore from keypad
Save to keypad
ID:
M6.5.1
STOP
READY
Keypad
I/O and Hardware
( 8 )
Main Menu
Favourites
( 0 )
User settings
( 4 )
ID:
M6
OK
OK