vacon • 111
Parameters
6
6.1.16
Group 3.16: Mainten. Counters
The maintenance counter is a way of indicating the operator that maintenance needs to be car-
ried out. For example, a belt needs to be replaced or oil in a gearbox should be changed.
There are two different modes for the maintenance counters, hours or revolutions*1000. The
counters are only incremented during Run mode in either case.
NOTE:
Revolutions are based
on motor speed which is only an estimate (integration every second).
When the counter exceeds the limit an alarm or fault will be trigged respectively. Individual
maintenance alarm and fault signals can be connected to a digital/relay output.
When maintenance has been carried out the counter can be reset through either a digital input
or a parameter B3.16.4.
Table 104. Maintenance counter parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.16.1
Counter 1 mode
0
2
0
1104
0 = Not used
1 = Hours
2 = Revolutions*1000
P3.16.2
Counter 1 alarm limit
214748
3647
80000
h/kRev
0
1105
When to trig a maintenance
alarm for counter 1.
0 = Not used
P3.16.3
Counter 1 fault limit
214748
3647
80000
h/kRev
0
1106
When to trig a maintenance
fault for counter 1.
0 = Not used
B3.16.4
Counter 1 reset
0
1
0
1107 Activate to reset counter 1.
P3.16.5
Counter 1 DI reset
Varies
Varies
0
490
TRUE = Reset
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......