Group 3.14: ExtPID Controller
6.1.15.1
Group 3.14.1: Basic settings
For more detailed information, see chapter 6.1.14.
P3.13.9.10
PID setpoint Reduct.
0.0
100.0
%
10.0
1694
Defines the rate of the PID
controller setpoint reduc-
tion when the Input pres-
sure supervision alarm is
active.
V3.13.9.11
InputPress. Monitor
Varies
Varies
Varies
Varies
1695
Monitoring value for
selected Input pressure
supervision signal.
Scaling value according to
P3.13.9.4.
Table 100. Basic settings for external PID-controller
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.14.1.1
Enable ExtPID
0
1
0
1630
0 = Disabled
1 = Enabled
P3.14.1.2
Start signal
DigIN
Slot0.2
1049
FALSE = PID2 in stop mode
TRUE = PID2 regulating
This parameter will have no
effect if PID2 controller is not
enabled in the Basic menu
for PID2
P3.14.1.3
Output in Stop
0.0
100.0
%
0.0
1100
The output value of the PID
controller in % of its maxi-
mum output value while it is
stopped from digital input
P3.14.1.4
Gain
0.00
1000.00
%
100.00
1631
P3.14.1.5
Integration Time
0.00
600.00
s
1.00
1632
P3.14.1.6
Derivation Time
0.00
100.00
s
0.00
1633
P3.14.1.7
ProcessUnitSel.
0
37
0
1635
P3.14.1.8
ProcessUnitMin
Varies
Varies
Varies
0
1664
P3.14.1.9
ProcessUnitMax
Varies
Varies
Varies
100
1665
P3.14.1.10
ProcessUnitDeci
0
4
2
1666
P3.14.1.11
Error inversion
0
1
0
1636
P3.14.1.12
Varies
Varies
Varies
0.0
1637
P3.14.1.13
0.00
320.00
s
0.00
1638
Table 99. Input pressure supervision parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
Summary of Contents for 100X series
Page 1: ...vacon 100 x ac drives Solar pump application manual ...
Page 2: ......
Page 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Page 8: ...2 vacon 5 Safety ...
Page 160: ...vacon 157 Parameters 6 ...
Page 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Page 170: ...7 vacon 167 Fault ...
Page 171: ......