Table 4. Parameters related with Modbus used through RTU
MONITORING VALUES
P5.7.3.2.1
Fieldbus protocol
status
1
3
1
0 = Init
1 = Stopped
2 = Operational
3 = Faulted
P5.7.3.2.2
Communication
status
0.0
99.999
0.0
0-99 Number of mes-
sages with errors
0-999 Number of mes-
sages without communi-
cation errors
P5.7.3.2.3
Illegal functions
0
P5.7.3.2.4
Illegal data
addresses
0
P5.7.3.2.5
Illegal data values
0
P5.7.3.2.6
Slave device busy
0
P5.7.3.2.7
Memory parity
error
0
P5.7.3.2.8
Slave device failure
0
P5.7.3.2.9
Last fault response
0
P5.7.3.2.10
Control word
hex
P5.7.3.2.11
Status word
hex
Code
Parameter
Min
Max
Unit
Default
ID
Description