6
vacon • 31
Communications
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Status Word bits
The Status word is composed of 32 bits. The meanings of bits are described below.
Table 20. Status Word bits B1-B28
Table 21. Status Word bits B29-B31, descriptions of bit connections
The use of process data depends on the application. In a typical situation, the device is started
and stopped with the ControlWord (CW) written by the Master and the Rotating speed is set with
Reference (REF). With PD1…PD8 the device can be given other reference values (e.g. Torque
reference).
With the StatusWord (SW) read by the Master, the status of the device can be seen. Actual Value
(ACT) and PD1…PD8 show the other actual values.
Bit
Name
Value = 1
Value = 0
Description
B0
Ready
Ready
Not ready
Indicates whether the drive is
ready or not
B1
Run
Running
Stop
Indicates whether the drive is
running or stopped
B2
Direction
Counterclockwise
Clockwise
Indicates the rotation direc-
tion of the motor
B3
Fault
Faulted
Not faulted
Indicates if a fault is active
B4
Alarm
Alarm
No alarm
Indicates if an alarm is active
B5
AtReference
True
False
Reference frequency reached
B6
ZeroSpeed
True
False
Motor running at zero speed
B7
FluxReady
True
False
Motor is magnetized
B8-B28 Not used
B29
Control place
B30
Control place
B31
Control place
Description
0
0
1
Fieldbus
0
1
0
Keypad
0
1
1
PC tool
1
0
0
I/O terminals
Summary of Contents for 100 INDUSTRIAL
Page 1: ......
Page 3: ...vacon 1 Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 7: ...1 vacon 5 Safety Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 11: ...3 vacon 9 Modbus technical data Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 27: ...5 vacon 25 Programming Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 43: ...7 vacon 41 Fault tracing Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 45: ...8 vacon 43 Quick setup Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 47: ......