6
vacon • 29
Communications
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Table 17. Fieldbus Process Data IN
Control word bits
The Control word is composed of 32 bits. Meanings of bits are described below. Unused bits
have to be set to zero.
Table 18. Control Word bits
2002
-
Reserved
Binary coded
2003
2053 = High data
2054 = Low data
FB Speed Reference
0…10000 %
2004
2055 = High data
2056 = Low data
FB Process Data In 1
See chapter 9.
2005
2057 = High data
2058 = Low data
FB Process Data In 2
See chapter 9.
2006
2059 = High data
2060 = Low data
FB Process Data In 3
See chapter 9.
2007
2061 = High data
2062 = Low data
FB Process Data In 4
See chapter 9.
2008
2063 = High data
2064 = Low data
FB Process Data In 5
See chapter 9.
2009
2065 = High data
2066 = Low data
FB Process Data In 6
See chapter 9.
2010
2067 = High data
2068 = Low data
FB Process Data In 7
See chapter 9.
2011
2069 = High data
2070 = Low data
FB Process Data In 8
See chapter 9.
*. In Vacon 100, the Control Word and the Status Word are formed of 32 bits. Only the initial 16
bits can be read in the 16-bit area.
Bit
Name
Value = 1
Value = 0
Description
B0
Start/Stop
Start request
Stop request
Start/Stop command to
application
B1
Direction
Reverse
Forward
Command to change
rotational direction
B2
Fault reset
Reset faults
No action
Command to reset fault
B3-B31 Not used
Address
Name
Range/Type
16-bit
*
32-bit
Summary of Contents for 100 INDUSTRIAL
Page 1: ......
Page 3: ...vacon 1 Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 7: ...1 vacon 5 Safety Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 11: ...3 vacon 9 Modbus technical data Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 27: ...5 vacon 25 Programming Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 43: ...7 vacon 41 Fault tracing Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 45: ...8 vacon 43 Quick setup Tel 358 0 201 2121 Fax 358 0 201 212 205...
Page 47: ......