ID 1766 Operating Time Trip Counter (years)
•
ID 1767 Operating Time Trip Counter (days)
•
ID 1768 Operating Time Trip Counter (hours)
•
ID 1769 Operating Time Trip Counter (minutes)
•
ID 1770 Operating Time Trip Counter (seconds)
Example: You receive the value 1a 143d 02:21 of the operating time trip counter from the
fieldbus.
•
ID1766: 1 (years)
•
ID1767: 143 (days)
•
ID1768: 2 (hours)
•
ID1769: 21 (minutes)
•
ID1770: 0 (seconds)
ID 2311 OPERATING TIME TRIP COUNTER RESET
You can reset the operating time trip counter with the PC, the control panel, or the fieldbus.
If you use the PC or the control panel, reset the counter in the Diagnostics menu.
If you use the fieldbus, to reset the counter, set a rising edge (0 => 1) to ID2311 Operating
Time Trip Counter Reset.
11.4.3
RUN TIME COUNTER
The run time counter of the motor cannot be reset. It is in the submenu Total counters. The
value of the counter has 5 different 16-bit values. To read the value of the counter through
fieldbus, use these ID numbers.
•
ID 1772 Run Time Counter (years)
•
ID 1773 Run Time Counter (days)
•
ID 1774 Run Time Counter (hours)
•
ID 1775 Run Time Counter (minutes)
•
ID 1776 Run Time Counter (seconds)
Example: You receive the value 1a 143d 02:21 of the run time counter from the fieldbus.
•
ID1772: 1 (years)
•
ID1773: 143 (days)
•
ID1774: 2 (hours)
•
ID1775: 21 (minutes)
•
ID1776: 0 (seconds)
11.4.4
POWER ON TIME COUNTER
The power on time counter of the power unit is in the submenu Total counters. It is not
possible to reset the counter. The value of the counter has 5 different 16-bit values. To read
the value of the counter through fieldbus, use these ID numbers.