![Vacon 100 flow Installation Instruction Download Page 9](http://html2.mh-extra.com/html/vacon/100-flow/100-flow_installation-instruction_3124435009.webp)
UK: VACON
®
100 drive supply switch
vacon • 7
24-hour s358 (0)201 212 575 • Email: [email protected]
uk
3. Cable requirements
The following table shows the maximum sizes for the cables to be used with the drive supply switch.
NOTE!
Use only copper cables with the drive supply switch option, no aluminium cables allowed!
* Cables with heat resistance of at least +90°C must be used.
4. Mechanical dimensions
Table 1. Cable data for the drive supply switch option
Frame
Type
Maximum mains
and motor cable
size (mm
2
)
Tightening torque of
the drive supply
switch screws (Nm)
Insulation tube size
for supply cable,
diameter/length (mm)
MR4
0003 2 - 0004 2
3 x 1.5 + 1.5
0.8
10/70
0006 2 - 0008 2
3 x 1.5 + 1.5
0011 2 - 0012 2
3 x 2.5 + 2.5
0003 5 - 0004 5
3 x 1.5 + 1.5
0005 5 - 0008 5
3 x 1.5 + 1.5
0009 5 - 0012 5
3 x 2.5 + 2.5
MR5
0018 2
3 x 6 + 6
0.8
16/80
0024 2
3 x 6 + 6
0031 2
3 x 10 + 10
0016 5
3 x 6 + 6
0023 5
3 x 6 + 6
0031 5
3 x 10 + 10
MR6
0048 2
3 x 16 + 16
2
20/80
0062 2
3 x 25 + 16
0038 5
3 x 10 + 10
0046 5
3 x 16 + 16
0061 5
3 x 25 + 16
MR7
0075 2
3 x 35 + 16
6
25/80
0088 2
3 x 35 + 16
0105 2
3 x 50 + 25*
0072 5
3 x 35 + 16
0087 5
3 x 35 + 16
0105 5
3 x 50 + 25*
Table 2. Mechanical dimensions of the drives with drive supply switch option
Drive size
Width (mm)
Height (mm)
Depth (mm)
Weight (kg)
MR4
128
328
270
6.5
MR5
144
419
295
10.5
MR6
195
557
302
20.5
MR7
237
660
332
38.5
Summary of Contents for 100 flow
Page 2: ......