Common Industrial Objects implemented by vacon® 100 family
vacon • 59
24-hour s358 (0)201 212 575 • Email: [email protected]
7
7.3.4.1
Changes from revision 1 to revision 2
The attributes FaultCode and FaultDay were changed from 8 bit to 16 bit.
7.3.4.2
Class Attributes
Class Attribute “Revision”
This attribute presents the revision of the Fault History Object which is implemented by the device.
The current revision is 2.
Class Attribute “Max Instance”
This attribute presents the maximum number of instances that can exist of the Fault History Object
in the device. The maximum value is 40.
Class Attribute “Number of Instances”
This attribute presents the number of instances that currently exist of the Fault History Object in the
device.
Class Ser-
vices
Id
Name
Description
1
Get_Attributes_All
Returns content of all (implemented)
attributes in the class.
5
Reset
Reset fault history
14
d
0E
h
Get_Attribute_Single
Used to read single attribute value.
Instance
Attributes
Id
Access rule
Name
Datatype
Description
1
Get
FaultCode
UINT
Fault code
2
Get
FaultID
UINT
Fault ID
3
Get
FaultYear
UINT
Fault date: Year
4
Get
FaultMonth
USINT
Fault date: Month
5
Get
FaultDay
UINT
Fault date: Day
6
Get
FaultMillisAfter
Midnight
UDINT
Fault date: Time, millisec-
onds after midnight
Instance
Services
Id
Name
Description
1
Get_Attributes_All
Returns content of all (implemented)
attributes in the instance
14
d
0E
h
Get_Attribute_Single
Used to read single attribute value
Table 51. Fault history object