SYSTEM PARAMETERS
VACON
•
57
24-hour support (0)201 212 575 • Email: [email protected]
9
9.9 System parameters
NOTE!
Parameters in bold are hidden, see P8.1.
Code
Parameter
Min
Max Default
ID
Note
Software information (MENU PAR -> S1)
S1.1
Software package
833
S1.2
Power SW version
834
S1.3
API SW version
835
S1.4
API Firmware
interface
836
S1.5
Application ID
837
S1.6
Application revision
838
S1.7
System load
839
(MENU PAR -> S2)
S2.1
Communication
status
808
Format: xx.yyy
xx = 0-64 (Number of error
messages)
yyy = 0 - 999 (Number of cor-
rect messages)
S2.2
Fieldbus protocol
0
1
0
809
0 = FB disabled 1= Modbus
S2.3
Slave address
1
255
1
810
S2.4
Baud rate
0
5
5
811
0=300, 1=600, 2=1200, 3=2400,
4=4800, 5=9600,
S2.5
Number of stop bits 0
1
1
812
0=1, 1=2
S2.6
Parity type
0
0
0
813
0= None (locked)
S2.7
Communication
time-out
0
255
10
814
0= Not used, 1= 1 second,
2= 2 seconds, etc.
S2.8
Reset communica-
tion status
815
1= Resets par. S2.1
Total counters
(MENU PAR -> S3)
S3.1
MWh counter
827
S3.2
Power on days
828
S3.3
Power on hours
829
User settings
(MENU PAR -> S4)
S4.1
Display contrast
0
15
7
830
Adjusts the display contrast
S4.2
Restore factory
defaults
0
1
0
831
1= Restores factory
defaults for all
parameters
Table 9.9: System parameters