25
SELF-DIAGNOSIS
The following error messages can be displayed on the segment display.
Error code
Cause
Solution
FL
Condensation tank
full
Discharge condensate according to the
“Condensate water manual draining” chapter.
E1
Defective exhaust
air temperature
sensor
Disconnect the device briefly from the mains.
Should the error still be displayed after the
restart, please contact the customer service.
E2
Defective room
temperature sensor
Disconnect the device briefly from the mains.
Should the error still be displayed after the
restart, please contact the customer service.
E4
Automatic defrost
At low ambient temperatures, ice may form at
the evaporator. The device will then carry out
an automatic defrost. The duration of the
defrost process can vary. Do not switch off the
device during automatic defrost. Do not
remove the mains plug from the mains socket.