92077r14
V200 POSITIONER
www.vacaccessories.com
9
2.4 Switch option Installation
2.4.1 Switch and cam installation
1. Remove the front cover and indicator
on the V200 positioner. (see page 4)
2. Remove the Indicator screw(1).
3. Install the switch cam assembly(2) in the
positioner drive slot and secure the cams with
screw(3). Install the switch module(4) and
tighten the three screws(5).
2.4.2 Electrical installation
Connect your control system/equipment cables
to the terminal blocks(6)
Maximum cable size AWG 11(4 mm
2
)
2.4.3 Switch calibration
The switch activating points can be adjusted by
turning the friction loaded cams(7,8) using a screw-
driver in the slots on the cams.
1. With a meter, set the first cam to either normally
open(NO) or normally closed(NC) at its desired
position.
2. Stroke the valve/actuator to the desired
position for the second switch and adjust
the second cam.
3. Double check the two activation points.
NOTE: Use a non magnetic screwdriver when
adjusting reed switch cams!
3
1
8
7
6
4
5
2