ENGLISH
23
DIP FUNCTION
SETTING
DESCRIPTION
8
Photocell
ON
Always active
Intervention of the photocell during opening or closing
causes the gate to stop. When the photocell restores, the
gate re-opens completely.
OFF
NOT active
during opening
Intervention of the photocell during opening is ignored.
Intervention of the photocell during closing causes the gate
to re-open completely.
9
Photocell test
ON
Enabled
The control unit performs a photocell operational test before
starting each opening or closing operation. If the photocells
are not operating correctly, the gate does not begin to move
and the light flashes for approx. 8 seconds.
PLEASE NOTE: connect the photocell TX correctly
OFF
Disabled
10
Safety edge
type
ON
Conductive
rubber edge
Select this option if using conductive rubber edges with
nominal resistance of 8K2.
OFF
Standard or
optical edge
Select this option if using standard edges with switch
normally closed or optical edges.
11
Safety edge
ON
Always active
Intervention of the edge during opening or closing causes
inversion of the direction of movement in order to free the
body that caused the edge to intervene. The gate will be
stopped after approx. 3 seconds.
OFF
NOT active
during opening
Intervention of the edge during opening is ignored.
Intervention of the edge during closing causes the gate to be
re-opened completely.
12
Safety edge
test
ON
Enabled
The control unit performs an operational test on the edges
before starting each opening or closing operation. If the
edges are not operating correctly, the gate does not begin to
move and the light flashes for approx. 8 seconds.
DO NOT enable testing if conductive rubber edges are
used or standard edges are used without a suitable
control unit for controlling function.
OFF
Disabled