VG-6791 Conventional Remote Indicator 

Installation and Operation Manual V1.01

 

2. Connect the wire from detector to Terminal A1 and A2.

3. Install the indicator cover on to Base and then rotate the cover to the locked position.

Wiring Details

1. Wiring Requirement: RVS-2*1.0 mm2 or1.5 mm2 wire, laid through metal tube (cable sink) or PVC

tube.

2.A1, A2 should connecting with detector base terminal 2 and 4 as Fig.3 (Non-polarized)

3. Please refer to the following figure for wiring on indicator base.

Testing

Warning

Power must be switched off before all devices are installed completely.

The detector must be tested after installation or regular maintenance for every 6 months.

Fire condition: After registration, make detector under fire conditions to test associated indicator

whether illuminated.

Reset

After testing, reset the indicator by resetting control panel.

Limited Warranty

Warrants that the product will be free of charge for repairing or replacing from defects in design, 

materials and workmanship during the warranty period. This warranty doesn’t cover any product that 

is found to have been improperly installed or used in any way not in accordance with the instructions 

supplied with the product. Anybody, including the agents, distributors or employees, is not in the 

position to amend the contents of this warranty. Please contact your local distributor for products not 

covered by this warranty. 

Company: V-GREAT GLOBAL CORPORATION 

Add.: Second Floor, Capital City, Independence Avenue, 

P.O. Box 1008, Victoria, Mahe, Seychelles 

Web

http://www.vgreatglobal.com

      Email: [email protected] 

O

-

O

+

Conventional Detector

Remote

Indicator

4.7

 E

nd

 o

f

Li

ne R

es
is

to

r

Conventional Detector

Remote

Indicator

Fig.4 

Fig.3 

Reviews: