VG-6637 Digital Heat Detector 

Installation and Operation Manual V1.03

 

 

The letter 

“R” suffix mean that the detector class incorporate a rate-of-risecharacteristic. It will give rapid 

response even when high rates of rise of air temperature starting at air temperaturessubstantially below the 
typical application temperature. 

 

TheVG-6637sensitivity  mode  can  be  set  by  Control  Panel,  please  refer  to  the  corresponding  Manual  for 
details. 

Testing 

Warning

Power is switched on after all devices are installed completely. 

The detector must be tested after installation or regular maintenance. 

 

Registration:

The  fire  alarm  control  panel  will  registers  the  detector  on  line  to  check  if  the  address  of  the 

detectors mounted is the same address as that registered in the control panel. 

 

Firecondition:

 After registration, make detector under fire conditions by using hot air generator to test 

whether the detector alarms normally and control panel displays its registered address. 

 

Reset

After testing, reset the detector through control panel. 

Fault Finding 

Detector Fault on Control Panel 

Check wiring of Common base, no water no short-circuits and open circuit. 

Check the connection between detector and common base. 

Nuisance alarm 

The detector still in alarm status if there is no Fire and other unusual,means it 
damaged. 

Address Fault 

Address is set incorrectly, Reset by VG-6532 Digital Programmer. 

 

Cautions 

1.  Dust 

cover  on  the  detector  shouldn’t  be  removed  between  installation  and  acceptance  test  to  avoid 

contamination. 

2. If the detector gives fault warning after a long operation, first check if the detector are damaged, or the position 
is changed. At last, other faults should be considered 

3. Fire alarm test requirement as specified in the applicable local codes, we suggest to test every 6 month. 

Please put on the dust cover if the room is decorated or wall-painted to avoid contamination. 

Limited Warranty 

Wewarrants that the product will be free of charge for repairing or replacing from defects in design, materials and 

workmanship  during  the  warranty  period.  This  warranty  doesn

’t  cover  any  product  that  is  found  to  have  been 

improperly installed or used in any way not in accordance with the instructions supplied with the product. Anybody, 

including  the  agents,  distributors  or  employees,  is  not  in  the  position  to  amend  the  contents  of  this  warranty. 

Please contact your local distributor for products not covered by this warranty. 

Reviews: