![UWT Vibranivo VN 4000 Series Technical Information/Instruction Manual Download Page 13](http://html1.mh-extra.com/html/uwt/vibranivo-vn-4000-series/vibranivo-vn-4000-series_technical-information-instruction-manual_1066148013.webp)
Level limit switch
Series VN 4000
Technical Information / Instruction manual
page G
Electrical installation
Connection
Connecting
terminals
Protective
Conductor
Terminal
3-wire
PNP
Power supply:
18 .. 50V DC ±10%*
*incl. ±10% of EN 61010
Input current: max. 0.5A
Fuse:
max. 4A, fast or slow, 250V
Signal output:
max. 0.4A
Output voltage equal to input
voltage, drop <2.5V
Load for example:
PLC, relay, contactor, bulb
PE Load - +
Power supply
Universal voltage
Relay DPDT
Power supply:
19..230V 50-60Hz ± 10%* 22VA
19..40V DC
± 10%* 2W
*incl. ±10% of EN 61010
Fuse on power supply:
max. 10A, fast or slow, HBC, 250V
Signal output:
Floating relay DPDT
AC max. 250V, 8A, non inductive
DC max. 30V, 5A, non inductive
Fuse on signal output:
max 10A, fast or slow, HBC, 250V
Signal output
- +
N L
Power supply
PE
Approved power supply with reinforced
insulation to mains is required
Vibranivo
®
1
2
3
4
5
6
7
8
9
10
11
12
VN 4000 a
gi161213
13