Level limit switch
Series RF 8000
Technical Information / Instruction manual
page
Operation - Electronic module: Standard
Settings
S1: Delay (covered to uncovered)
S3: Failsafe High/Low
S4: Test
S5: Sensitivity High/Low
P1
P2
switch point
DIP switches
L2
red
delay
Use the delay function to slow the signal output response, and compensate for turbulence or false readings.
S1 / S2: Signal output delay
S3: Failsafe High / Low
Failsafe Mode
S3
Failsafe High
Failsafe Low*
relay
switch
relay
switch
relay
switch
relay
switch
*Factory setting
*Factory setting
S2: Delay (uncovered to covered)
S1
S2
Delay
active*
Delay
off
Delay
active*
Delay
off
Signal output delay:
Sensor covered to uncovered
Signal output delay:
Sensor uncovered to covered
Delay time / seconds
DIP switches
L3
green
L1
yellow
*Factory setting
LEDs
L1: Sensor status (yellow)
ON if sensor is detected as covered (capacitance on sensor is greater than setted switch point)
L2: Signal output (red)
ON if Relay is activated / Solid state switch is closed.
L3: Power supply (green)
ON if power is present
1
2
3
4
5
6
7
8
9
10
11
12