Level limit switch
Series RF 8000
Technical Information / Instruction manual
page
Electrical installation
1. Loosen the lid clip and unscrew the lid of the enclosure.
2. Unscrew and lift up the digital display (loosen each screw two
turns before completely loosening both, to keep the rubber
retaining rings in place.)
3. Connect the wires to the terminals
4. Ground the instrument according to local regulations.
5. Tighten the cable gland to form a good seal.
6. Fix the digital display.
7. To adjust the transmitter locally, using the keypad, go to
Programming via the Local User Interface (LUI).
After adjustment, replace the enclosure lid and tighten the lid clip.
Power supply
or Profibus PA
Solid state
switch
Digital display
Electronic module: Digital
(Profibus PA / Solid State)
Power supply
or Profibus PA*
(polarity not important)
internal
wiring
Solid state switch
(polarity not important)
internal
wiring
blue
blue
red
black
white
Protection diode
Observe a Protection diode in case of
connecting an external relay to the Solid
state switch
Protection of Solid State Switch:
Solid
state
switch
* With use of Profibus PA the wiring must be
according to Profibus PA standards.
If Profibus PA is not used, a shielded cable is
recommended to ensure stable measurement.
Power supply:
12 .. 30 V DC, 12.5 mA
Intrinsically Safe:
12 .. 24 V DC, 12.5 mA
Intrinsically safe barrier required
For ATEX: U
i
=24 V, I
i
=380 mA, P
i
=5.32 W, C
i
=5 nF, L
i
=10 uH
For FM/ CSA: See "Connection drawing on page 23"
Signal output:
Solid state switch:
30 V DC or 30 V AC (peak), 82 mA
Observe protection (see below)
Intrinsically safe:
Intrinsically safe barrier required
For ATEX: U
i
=30 V, I
i
=200 mA, P
i
=350 mW, C
i
=0, L
i
=0
For FM/ CSA: See "Connection drawing on page 23"
Connecting the electronic module:
1
2
3
4
5
6
7
8
9
10
11
12
c RF 8000
gi150917
22
RFnivo
®