C-00829 USJJ-005 Manual Rev. 6.5 (8-15-14)

Safety Procedures

Follow all basic and necessary procedures to secure the electrical site before beginning 

work. Follow all existing codes, requirements and instructions for all equipment used 

in conjunction with the Jack Jumper™ Cutout Bypass Tool. Inspect the cutout carefully 

for damaged or corroded arcing horns, arcing bars or fuse doors. If arcing horns are 

corroded use standard electrical procedures to clean the arcing horns prior to utilizing 

the Jack Jumper™ Cutout Bypass Tool.
Inspect the porcelain for any damage or cracks. If either condition is found, do not use 

the Jack Jumper™ Cutout Bypass Tool.

!

!

WARNING

Never install or remove Jack Jumper™ Cutout Bypass Tool without a 

working fuse in place. It is not a switch and should never be used as one.

If emergency arises, follow the standard safety operating procedures for your facility.
The Jack Jumper™ Cutout Bypass Tool should be stretched slightly and visually 

inspected prior to utilization to ensure that the copper coil is not frayed or separated. If 

fraying or separation of the copper coil has occurred do not utilize the tool.

!

!

WARNING

Only install the Jack Jumper™ Cutout Bypass Tool with the use of an 

insulated shotgun stick. When attaching or detaching the Jack Jumper™ 

Cutout Bypass Tool do not use abrupt or rough movements, be gentle 

and do not hurry.

!

!

WARNING

If you are servicing a fuse, replace the fuse as quickly as possible. 

The fuse is a protective device. The Jack Jumper™ Cutout Bypass Tool 

DOES NOT FUNCTION AS A FUSE. If you must leave the area, 

replace any fuses and remove the Jack Jumper™ Cutout Bypass Tool. 

It is not a fuse replacement or permanent by-pass mechanism.

Summary of Contents for Jack Jumper SMD-20

Page 1: ...ss Tool C 00829 USJJ 005 Manual Rev 6 5 8 15 14 USJJ 005 38 kV Cutout Bypass Tool 15 kV SMD 20 Power Fuse Bypass Tool Operation Maintenance Manual Contents Product Description 4 Product Line 4 Safety...

Page 2: ...an result in death grievous personal injury and or equipment damage WARNING Follow safe work procedures and practices when utilizing this device Failure to use this device in a safe manner can result...

Page 3: ...is used to bypass cutouts on both overhead lines and underground taps For 200 Ampere SMD 20 systems attach two Jack Jumper Cutout Bypass Tools on opposite sides of the SMD 20 Power Fuse this only wor...

Page 4: ...lace It is not a switch and should never be used as one If emergency arises follow the standard safety operating procedures for your facility The Jack Jumper Cutout Bypass Tool should be stretched sli...

Page 5: ...utout Figure A 4 Be sure the Jack Jumper Cutout Bypass Tool is secure and will not interfere with removal of the fuse 5 Release the top ring 6 Grasp the bottom in line ring of the Jack Jumper Cutout B...

Page 6: ...r Cutout Bypass Tool with the shotgun stick 7 Gently pull to expand the spring and hook the bottom attachment hook on the lower fuse door hinge casting Figure D The Jack Jumper Cutout Bypass Tool is n...

Page 7: ...ntenance disassembly or misuse voids any and all warranties guarantees or liability Warranty Utility Solutions warrants the Jack Jumper Cutout Bypass Tool for any defects in manufacturing for the peri...

Page 8: ...8 C 00829 USJJ 005 Manual Rev 6 5 8 15 14...

Reviews: