17
AVOID THE FOLLOWING
Dead Spots
Corners
Alcoves
Behind doors
Cold Spots
Concealed pipes or ducts
Stairwells - drafts
Unheated rooms on the other side
of the wall
Hot Spots
Concealed pipes
Fireplaces
TVs or radios
Lamps
Direct sunlight
Kitchens
Set heat anticipator at 0.7 amps. Connect 24 volt thermostat
leads to the two (2) yellow wires located in service switch
junction box, located on outer jacket of boiler. See Figure
#13 for service switch junction box and thermostat fi eld
wiring connections.
Connect Circulator Pump Wiring
See Figures #14A & #14B for service switch junction
box and circulator pump fi eld wiring connections. If the
two 120 volt circulator wire terminals inside the junction
box are not used, please leave the two wire nuts to prevent
the short circuit.
!
CAUTION
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
Run 14 gauge or heavier copper wire from boiler to
grounded connection in service panel or properly driven
and electrically grounded ground rod.
Installing The Thermostat
Thermostat location has important effect on
operation of your boiler system. BE SURE TO
FOLLOW INSTRUCTIONS INCLUDED WITH YOUR
THERMOSTAT.
Locate thermostat about fi ve feet above fl oor on inside
wall. It may be mounted directly on wall or on vertical
mounted outlet box. It should be sensing average room
temperature.
ELECTRICAL WIRING
Summary of Contents for UB90 125
Page 30: ...30 SERVICE HINTS DETAILED SEQUENCE OF OPERATION ...
Page 36: ...36 Troubleshooting Chart 2 TROUBLESHOOTING ...
Page 39: ...39 Troubleshooting Chart 5 TROUBLESHOOTING ...
Page 42: ...42 This Page Intentionally Left Blank ...
Page 44: ...UTICA BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...