43
PI
9.10 De-Aeration Function
Used to eliminate air inside the heating circuit when boiler
is installed or after maintenance when water is drained from
primary circuit.
1.
Press buttons
together and hold for 6 seconds.
On
appears on display for a few seconds, followed by
program row
312
.
2.
The electronic board will activate pump on/off cycle for 10
minutes. Function will automatically stop at end of cycle.
3.
To manually exit this function, press
buttons
together and hold for 6 seconds.
9.11 Commission Set Up (Gas) - Changing The Type
Of Gas
During the
first
installation boiler carries out an automatic
commissioning function.
The system is able to detect the gas type present in the
network.
Correct gas type setting, is made by pressing two buttons at
the same time, see section 9.7 Commissioning.
Change of gas type is made
after
the first installation:
•
Change parameter P02. See section 9.7 Commissioning
and section 9.13 Parameter Settings.
•
At Maximum fire rate, check minimum gas pressure is
suitable for selected gas:
Gas A (NG) = 3.5" (8.7 mbar)
Gas E (LPG) = 8.0" (19.9 mbar)
•
Place supplied label with indication of gas type close to
the data plate of boiler replacing the original.
•
Perform Automatic Calibration Function -
Section 9.8.
•
Manufacturer recommends
verification of CO
2
concentration
on the flue.
FIGURE 9-3 - Gas Inlet Tap - Pi
PI = Gas Supply Inlet Pressure Tap
9 - START UP PROCEDURE
PI
IMPORTANT INFORMATION
A. If gas recognition function is interrupted by power
blackout, start function again when power is restored.
Press
and
together and hold at same time for at
least 6 seconds.
B. If display shows fault
E118
(low pressure in hydraulic
circuit) during gas recognition function, open filling tap
on appliance and restore correct pressure.
C. If gas recognition function is interrupted due
to fault (e.g.:
E133
no gas) press
to
reset. Then press
and
(for at least
6 seconds) to restart the function again.
If gas recognition function is interrupted due to
overheating, restart function by pressing and holding
down together for at least 6 seconds.
D. Combustion of this appliance has been factory controlled,
calibrated and set for operation with
Gas A
(Natural
Gas).
E. During Gas Type Control Function, combustion ratio will
increase for a short period of time while gas type is being
established.
9.9 Manual Calibration Function:
Manual Calibration phase starts at the end of the Automatic
Calibration.
The Display shows the boiler power and adjustment of the
CO2 value (parameter setting) during Manual Calibration
sequence.
The process begins at minimum power.
A. After Automatic Calibration sequence with
flashing together on the display, you can adjust
minimum power combustion by pressing
to lower %
CO
2
, and
to raise % CO
2
.
B. When minimum power combustion is in the specified
range, press
and then
to reach ignition power.
C.
Press
to adjust ignition power combustion. Press
to lower % CO
2
, and
to raise % CO
2
.
D. When ignition power combustion is in the specified
range, press
and then
to reach maximum power.
E.
Press
to adjust maximum power combustion. Press
to lower % CO
2
, and
to raise % CO
2
.
F. When maximum power combustion is in the specified
range, press
to exit Manual Calibration Function.
240012874 REV A, [01/31/2020]
Summary of Contents for MACF-150
Page 63: ...61 A 1 MODELS 125 Heat Only APPENDIX A WIRING DIAGRAMS 240012874 REV A 01 31 2020 ...
Page 64: ...62 APPENDIX A WIRING DIAGRAMS A 2 MODELS 165 Heat Only 240012874 REV A 01 31 2020 ...
Page 65: ...63 A 2 MODELS 150 Combi APPENDIX A WIRING DIAGRAMS 240012874 REV A 01 31 2020 ...
Page 66: ...64 A 4 MODELS 205 Combi APPENDIX A WIRING DIAGRAMS 240012874 REV A 01 31 2020 ...
Page 67: ...65 NOTES 240012874 REV A 01 31 2020 ...
Page 68: ...66 NOTES 240012874 REV A 01 31 2020 ...
Page 99: ...29 MODEL 150F Combi 150F FLOOR STANDING COMBI WIRING DIAGRAM PN 240012875 REV A 01 31 2020 ...
Page 101: ...31 205F FLOOR STANDING COMBI WIRING DIAGRAM MODEL 205F Combi PN 240012875 REV A 01 31 2020 ...
Page 106: ...36 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240012875 REV A 01 31 2020 ...