22
Boiler Model:
Boiler Serial Number:
Date of Installation:
Measured BTUH Input:
Boiler Location:
Altitude of Location:
Honeywell AM Kit Installed? (Yes/No):
Service Dates:
System Type (Give Brief Description):
installation instructions Have Been Followed
•
Checkout Procedure/Adjustments Performed
•
Maintenance/Service Issues Reviewed With Owner or Maintenance Person
•
Installation Manual Affixed Adjacent To or On Boiler
•
Installer/Technician’s Company:
Installer’s Name:
Company Address:
Company Phone Number:
Installer’s Signature:
HARD LOCKOUT MODE
Boiler in hard lockout (requires manual RESET)
Display flashes first digit
E
E
and last two digits (lockout code)
(see below)
xx
Code
Reason for hard lockout
Code
Reason for hard lockout
00
Flame detected on start-up
18
Supply water temperature higher than 200°F
02
Ignition failed after 5 retries
19
Return water temperature higher than 190°F
03
gas valve disconnected
25
Outlet temperature increased too fast
04
Power lost after lockout
28
No signal from blower; blower not running or defective blower motor
05
internal control failure
29
Blower signal not “0” when it should be
06
internal control failure
30
Max difference (b30) was too large for 20 successive times. Non
adjustable default max delta set to 100°F.
07
internal control failure
31
Outlet temperature sensor short circuit
11
internal control error
32
Return temperature sensor short circuit
12
Casting temperature switch open
36
Outlet temperature sensor open circuit
13
internal control failure
37
Return temperature sensor open circuit
14
internal control failure
44
internal control failure
15
internal control failure
60
Internal error reading parameters
16
internal control failure
61
Air flow circuit failure
17
internal control failure
65
Not enough blower driving force