1 Style Y Class B Agent Release Circuit 

>>

Programmable to operate (a) 1 or 2 ganged 24
Vdc Kidde Solenoid Control Heads for clean
agent or CO

2

 systems or (b) 1 FM Group A, B, D,

E or G Solenoid for Deluge/Pre-Action Systems.

>>

A second programmable Release Circuit is also
provided to operate 1 Stop Valve for systems
using Clustered Agent Cylinders (a common cyl-
inder bank protects multiple hazards and Stop
Valves direct Agent to the affected area).

Relay Outputs

>>

1 Form C System Alarm Relay

>>

1 Form C System Trouble Relay

>>

1 Form C Programmable Relay

Optional Relay Board (ORB)

>>

5 Form C Programmable Relays

MCP CONSTRUCTION

The MCP enclosure is designed for surface mounting
and is rated NEMA 1 for indoor use. It is constructed of
18 Gauge steel, painted red and kept closed by a steel
door with a key-lock. All operator interface switches and
indicators are located behind the locked cover. The
enclosure is large enough to house two 12 AH 12 Vdc
batteries for backup power supply. Battery Enclosures
are available for larger capacity batteries. A trim-ring is
available for flush mounting.

REMOTE HAZARD UNIT (RHU)

RHU POWER SUPPLY

The Power Supply Unit in the RHU is the same unit as in 
the Main Control Panel.

RHU DISPLAY-CONTROL MODULE

Remote Hazard Units are available either with or without
a Display-Control Module. When used, as shown in Fig-
ure 4, the RHU Display-Control Module is similar to that
of the MCP with the exception of the Menu Control but-
tons, which are provided only on the MCP. RHU Displays
can be programmed to operate either in local or global
mode.

Figure 4.  RHU Display-Control Module

RHU INPUT AND OUTPUT CIRCUITS

Each RHU is also a Single Hazard Panel and is similar to
the Main Control Panel being provided with the same
Input and Output Circuits (with the exception of the three
System Relays). The Optional Relay Board (ORB) can
also be mounted to the RHU.

RHU CONSTRUCTION

When using the optional Display-Control Module, the
RHU Enclosure is similar to that of the MCP. If this option

SIGNAL

SUPERVISORY

POWER ON

ALARM

UNIT

TROUBLE

SIGNAL

SUP/TBL
SCROLL

REMOTE

HAZARD

ALARM
SCROLL

CONTROLS

SYSTEM

RESET

SILENCE

SILENCED

R

R

RHU

v1.AD

LOCAL STATUS NORMAL

12:00

ALM00

SUP0

TBL00

09-17-02

Detection Circuit # 1

Style B or D

Detection Circuit # 2
Style B or D

Smoke and

Heat Detectors

Waterflow Input

Style B or D

Sprinkler System

Pull Station

Manual Release

Abort

Style B

Abort Station

Supervisory Signal

Release Circuit

Auxiliary Power 1

24 Vdc

24 Vdc

(Not resettable)

Auxiliary Power 2

Inputs from

field devices

Outputs

RS485

Port

RS-485 Data Highway

1 or 2 Clean Agent Control Heads

1 Deluge System Solenoid

1 or 2 C

System Control Heads

O

2

To Remote Display Units

To and from other

System Units

Form C Alarm Relay

Form C Trouble Relay

Form C Prog. Relay

Auxiliary Functions

- Equipment Shutdown
- Repeat Annunciation
- DACT (MCP only)

PUSH

PULL

FIRE

FIRE

PUSH / HOLD

SUPPRESSION

SYSTEM ABORT

Style B

Style B

5 Form C Prog. Relays
on Option Relay Board

Indicating Circuit # 1

Style Y or Z

Indicating Circuit # 2

Style Y or Z

Audible and Visual

Indicating Devices

All relays except those on ORB
are applicable to the MCP only.

KIDDE

Style Y

AGENT

RELEASING

LOGIC

Figure 3.  MCP and RHU Hazard Block Inputs and Outputs

Summary of Contents for Kidde Fire Systems Gemini II Multi-Hazard

Page 1: ...re 1 this basic system can be field expanded to be a large eight hazard Control Display System with up to seven Remote Hazard Units RHU and sixteen Remote Display Units RDU all of which reside on a fault tolerant communications network The MCP and each RHU is intended to be physically located in the space it is meant to protect Since the MCP and RHUs are computer controlled each one can act in sta...

Page 2: ...al hardware Rated 2 5 Amps total at 24 Vdc for polarized Audio Visual devices Individually programmable to operate on 1st Alarm Waterflow Agent Pre Release Manual Release and Agent Release conditions and to generate Silent Steady 60 bpm Pulse 120 bpm Pulse and Temporal sound patterns either in Silenceable or Non Silenceable mode MAIN CONTROL PANEL POWER ON ALARM TROUBLE SUPERVISORY SIGNAL SILENCED...

Page 3: ... be programmed to operate either in local or global mode Figure 4 RHU Display Control Module RHU INPUT AND OUTPUT CIRCUITS Each RHU is also a Single Hazard Panel and is similar to the Main Control Panel being provided with the same Input and Output Circuits with the exception of the three System Relays The Optional Relay Board ORB can also be mounted to the RHU RHU CONSTRUCTION When using the opti...

Page 4: ... Display Modules Each LED Display Module pertains to one zone of protection and provides 16 zone specific LEDs over and above the five System LEDs provided on the MCP Display Control Module Enclosures of ULC listed MCP and RHU units are provided dead front pan els POWER RDU v1 AD SYSTEM STATUS NORMAL 12 00 09 17 02 ALM00 SUP0 TBL00 REMOTE DISPLAY UNIT R R ALARM SCROLL SUP TBL SCROLL SYSTEM CONTROL...

Page 5: ...to upload feature enhancements to its operating system The ISP Utility CD ROM operates on IBM compatible computers running Windows 95 98 2000 XP ME or NT and is con nected to the ISP port on the MCP RHU and RDU via Kidde P N 74 100016 003 PEGAsys Telephone Cable with DB9 Adapter TECHNICAL SPECIFICATIONS MAIN CONTROL PANEL MCP REMOTE HAZARD UNITS RHU REMOTE DISPLAY UNITS RDU Main Menu Set List Isol...

Page 6: ...zard Unit w o Display RHU ULI 120 240 Vac 50 60 Hz Input Networked Unit controls 1 Hazard Block NEMA 1 Enclosure will house two 12 Vdc 12 AH Bat teries order selected batteries separately 84 322002 002 Gemini II Remote Hazard Unit with Display RHU ULI ULC 120 240 Vac 50 60 Hz Input Networked Unit controls 1 Hazard Block NEMA 1 Enclosure with dead front will house two 12 Vdc 12 AH Batteries order s...

Reviews: