- 3 -
•
1 Style Y Class B Agent Release Circuit
>>
Programmable to operate (a) 1 or 2 ganged 24
Vdc Kidde Solenoid Control Heads for clean
agent or CO
2
systems or (b) 1 FM Group A, B, D,
E or G Solenoid for Deluge/Pre-Action Systems.
>>
A second programmable Release Circuit is also
provided to operate 1 Stop Valve for systems
using Clustered Agent Cylinders (a common cyl-
inder bank protects multiple hazards and Stop
Valves direct Agent to the affected area).
•
Relay Outputs
>>
1 Form C System Alarm Relay
>>
1 Form C System Trouble Relay
>>
1 Form C Programmable Relay
•
Optional Relay Board (ORB)
>>
5 Form C Programmable Relays
MCP CONSTRUCTION
The MCP enclosure is designed for surface mounting
and is rated NEMA 1 for indoor use. It is constructed of
18 Gauge steel, painted red and kept closed by a steel
door with a key-lock. All operator interface switches and
indicators are located behind the locked cover. The
enclosure is large enough to house two 12 AH 12 Vdc
batteries for backup power supply. Battery Enclosures
are available for larger capacity batteries. A trim-ring is
available for flush mounting.
REMOTE HAZARD UNIT (RHU)
RHU POWER SUPPLY
The Power Supply Unit in the RHU is the same unit as in
the Main Control Panel.
RHU DISPLAY-CONTROL MODULE
Remote Hazard Units are available either with or without
a Display-Control Module. When used, as shown in Fig-
ure 4, the RHU Display-Control Module is similar to that
of the MCP with the exception of the Menu Control but-
tons, which are provided only on the MCP. RHU Displays
can be programmed to operate either in local or global
mode.
Figure 4. RHU Display-Control Module
RHU INPUT AND OUTPUT CIRCUITS
Each RHU is also a Single Hazard Panel and is similar to
the Main Control Panel being provided with the same
Input and Output Circuits (with the exception of the three
System Relays). The Optional Relay Board (ORB) can
also be mounted to the RHU.
RHU CONSTRUCTION
When using the optional Display-Control Module, the
RHU Enclosure is similar to that of the MCP. If this option
SIGNAL
SUPERVISORY
POWER ON
ALARM
UNIT
TROUBLE
SIGNAL
SUP/TBL
SCROLL
REMOTE
HAZARD
ALARM
SCROLL
CONTROLS
SYSTEM
RESET
SILENCE
SILENCED
R
R
RHU
v1.AD
LOCAL STATUS NORMAL
12:00
ALM00
SUP0
TBL00
09-17-02
Detection Circuit # 1
Style B or D
Detection Circuit # 2
Style B or D
Smoke and
Heat Detectors
Waterflow Input
Style B or D
Sprinkler System
Pull Station
Manual Release
Abort
Style B
Abort Station
Supervisory Signal
Release Circuit
Auxiliary Power 1
24 Vdc
24 Vdc
(Not resettable)
Auxiliary Power 2
Inputs from
field devices
Outputs
RS485
Port
RS-485 Data Highway
1 or 2 Clean Agent Control Heads
1 Deluge System Solenoid
1 or 2 C
System Control Heads
O
2
To Remote Display Units
To and from other
System Units
Form C Alarm Relay
Form C Trouble Relay
Form C Prog. Relay
Auxiliary Functions
- Equipment Shutdown
- Repeat Annunciation
- DACT (MCP only)
PUSH
PULL
FIRE
FIRE
PUSH / HOLD
SUPPRESSION
SYSTEM ABORT
Style B
Style B
5 Form C Prog. Relays
on Option Relay Board
Indicating Circuit # 1
Style Y or Z
Indicating Circuit # 2
Style Y or Z
Audible and Visual
Indicating Devices
All relays except those on ORB
are applicable to the MCP only.
KIDDE
Style Y
AGENT
RELEASING
LOGIC
Figure 3. MCP and RHU Hazard Block Inputs and Outputs