background image

3

95-8549

8.3

CAUTION

These tests require disabling of all extinguishing 
devices to avoid release resulting from a 
successful test.

The magnetic 

oi

 test is performed by placing a magnet by 

the marked location (mag 

oi

) on the outside of the detector.  

The manual 

oi

 test is accomplished by connecting the 

oi

 

lead (terminal 22) to power supply minus via an external 

switch. The magnet or switch must be held in place for 

a minimum of 6 seconds to complete the test. Either of 

these test methods activates the calibrated UV emitter.  

If the resulting signal meets the test criteria, indicating 

that greater than half of the detection range remains, the 

Alarm relay changes state, the indicating LED changes 

to red, and the 0-20 mA current output goes to 20 mA.  

This condition remains until the magnet is removed or the 

switch is released, regardless of whether the relays are 

set for latching or non-latching operation.

If less than half of the detection range remains, no alarm 

is produced and a fault is generated.  The fault indication 

can be reset by momentarily applying the magnet or 

manual 

oi

 switch.

NOTE

Refer to Appendix A for FM verification of 
Det-Tronics’ Optical Integrity 

oi

 function.

COMMUNICATION

The X2200 is furnished with an RS-485 interface for 

communicating status and other information with external 

devices.  The RS-485 supports MODBUS protocol, with 

the detector configured as a slave device.

NOTE

The EQP model uses LON/SLC communication.  
RS-485 communication is not available on the 
EQP model.

DATA LOGGING / EVENT MONITORING

Data logging for event monitoring capability is also 

provided.  The detector can log up to 1500 events 

(up to 1000 general and 500 alarm events).  Status 

conditions such as normal, power down, general and 

oi

 faults, pre-alarm, fire alarm, time and temperature 

are recorded.  Each event is time and date stamped, 

along with the temperature and input voltage.  Event 

data is stored in non-volatile memory when the event 

becomes active, and again when the status changes.  

Data is accessible using the RS-485 port or the EQP 

controller.

INTEGRAL WIRING COMPARTMENT

All external wiring to the device is connected within 

the integral junction box.  The screw terminals accept 

wiring from 14 to 24 AWG.  The detector is furnished with 

four conduit entries, with either 3/4 inch NPT or 25 mm 

threads.

SIGNAL PROCESSING OPTIONS

The UV detector output (measured in counts per second) 

is compared to the fire threshold (the "sensitivity" setting).  

If the radiant energy level from the fire exceeds the 

selected alarm threshold level, the fire alarm output is 

activated.  In every application, it is crucial to ensure that 

the radiant ultraviolet energy level from the expected fire 

at the required distance from the detector will exceed the 

selected sensitivity level.

The UV detector in the X2200 can be programmed for:

 

Arc Rejection

 

Standard Signal Processing.

Arc Rejection (Recommended Factory Setting)

The Arc Rejection mode enables the detector to prevent 

nuisance fire alarms caused by UV from short-duration 

electrical arcs or electrostatic discharge, while maintaining 

the ability to reliably detect the UV given off by a flame.  

Typical applications that benefit from arc rejection logic 

include electrostatic coating processes and uncontrolled 

environments where transient UV sources can be present, 

such as many typical outdoor applications.  Most false 

alarm sources have short transient UV signatures, while 

fire creates a long UV signature over many seconds.  

Most fires are detected in a few seconds (see response 

times in Appendix A).

Standard Signal Processing

Standard signal processing is recommended for 

high-speed suppression systems only.  To allow for 

high-speed operation, the standard processing mode 

does not incorporate the arc rejection programming.  

This mode should only be used in a controlled, indoor 

environment.

Summary of Contents for Det-Tronics X2200

Page 1: ...Instructions 95 8549 UV Flame Detector X2200 8 3 Rev 6 10 95 8549 ...

Page 2: ...6 Detector Orientation 6 Protection Against Moisture Damage 6 Wiring Procedure 7 EOL Resistors 8 Setting Device Network Addresses EQ and EQP Models Only 13 STARTUP PROCEDURE 14 Fire Alarm Test 14 TROUBLESHOOTING 14 MAINTENANCE 15 Cleaning Procedure 15 oi Plate Removal 15 Periodic Checkout Procedure 15 Clock Battery 15 FEATURES 16 SPECIFICATIONS 16 REPLACEMENT PARTS 19 DEVICE REPAIR AND RETURN 19 O...

Page 3: ...door applications The standard output configuration includes fire fault and auxiliary relays Output options include 0 to 20 mA output in addition to the three relays Pulse output for compatibility with existing controller based systems with fire and fault relays Eagle Quantum Premier EQP compatible model no analog or relay outputs HART Communication A tricolor LED on the detector faceplate indicat...

Page 4: ...es personnel of fire alarm or fault conditions Table 2 indicates the condition of the LED for each status OPTICAL INTEGRITY oi Automatic oi The X2200 includes the Automatic Optical Integrity oi feature a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities No testing with an external test lamp is required The detector automa...

Page 5: ...e and date stamped along with the temperature and input voltage Event data is stored in non volatile memory when the event becomes active and again when the status changes Data is accessible using the RS 485 port or the EQP controller INTEGRAL WIRING COMPARTMENT All external wiring to the device is connected within the integral junction box The screw terminals accept wiring from 14 to 24 AWG The d...

Page 6: ...olar radiation However it will respond to sources of UV besides fire such as electric arc welding lightning high voltage corona x rays and gamma radiation FACTORS INHIBITING DETECTOR RESPONSE Windows Glass and Plexiglas windows significantly attenuate UV radiation and must not be located between the detector and a potential flame source If the window cannot be eliminated or the detector location c...

Page 7: ...r before activating the system ATTENTION Observe precautions for handling electrostatic sensitive devices The following is a partial list of compounds that exhibit significant UV absorption characteristics These are also usually hazardous vapors While generally of little consequence in small amounts these gases can restrict UV detection if they are in the atmosphere in heavy concentrations It shou...

Page 8: ...UV radiation and reduce the sensitivity of the detector Verify that all detectors in the system are properly aimed at the area to be protected The Det Tronics Q1201C Laser Aimer is recommended for this purpose If possible fire tests should be conducted to verify correct detector positioning and coverage For ATEX installations the X2200 detector housing must be electrically connected to earth groun...

Page 9: ...ed cable is recommended Wires should be stripped 3 8 inch 9 mm A minimum input voltage of 18 Vdc must be present at the X2200 NOTE Refer to Power Consumption in the Specifications section of this manual The use of shielded cable is required to protect against interference caused by EMI and RFI When using cables with shields terminate the shields as shown in Figures 7 through 12 and Figure 14 Consu...

Page 10: ...s must be ceramic wirewound type rated 5 watts minimum with actual power dissipation not to exceed 2 5 watts This applies to ATEX IEC installations only 2 Resistor leads should be cut to a length of approximately 1 1 2 inches 40 mm 3 Bend the leads and install the EOL resistor as shown in Figure 6 4 Maintain a 3 8 inch 10 mm minimum gap between the resistor body and the terminal block or any other...

Page 11: ...6 25 24 23 22 21 SPARE SPARE RS 485 A RS 485 B MAN Oi 4 20 mA 4 20 mA 4 20 mA REF 4 20 mA REF COM AUX N O AUX N C AUX Figure 7 Ex d Wiring Option B2152 FIRE ALARM PANEL X2200 DETECTOR ALARM ALARM 24 VDC WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN N O AND COMMON COM CONTACTS ARE CLOSED 2 ALARM RELAY IS NORMALLY DE ENERGIZED WIT...

Page 12: ... mA Current Output Sinking 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC C2155 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 29 28 27 26 25 24 23 22 21 MAN Oi X2200 DETECTOR 24 VDC 24VDC 24VDC 24VDC Figure 11 X2200 Detector Wired for Isolated 0 to 20 mA Current Output Sourcing 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC C2156 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 ...

Page 13: ...dresses section of this manual for switch setting procedure 5 Check all field wiring to be sure that the proper connections have been made 6 Replace the device cover 7 Make the final sighting adjustments and ensure that the mounting bracket hardware is tight NOTE Refer to the Eagle Quantum Premier system manual number 95 8533 for information regarding power and network communication cable requirem...

Page 14: ...2 COM1 P1 P2 P3 P4 IN OUT B B COMMON C C SUPPLY A A CH 1 CH 5 IN OUT B B COMMON C C SUPPLY A A CH 2 CH 6 IN OUT B B COMMON C C SUPPLY A A CH 3 CH 7 IN OUT B B COMMON C C SUPPLY A A CH 4 CH 8 CONTROLLER 24 VDC 4 2 24 VDC 3 1 B 52 49 A 53 50 TxD A 59 56 RxD B 58 55 GND GND 57 54 SHIELD 51 48 COM2 COM1 P1 P7 P9 P8 P4 P5 1 5 5 13 1 5 6 14 2 6 7 15 2 6 8 16 3 7 9 17 3 7 10 18 4 8 11 19 4 8 12 20 P2 P3 ...

Page 15: ...ess to the network address switches For hazardous areas the area must be de classified before attempting disassembly of the device Always observe precautions for handling electrostatic sensitive devices The address number is binary encoded with each switch having a specific binary value with switch 1 being the LSB Least Significant Bit See Figure 16 The device s LON address is equal to the added v...

Page 16: ...windows 3 Check input power to the unit 4 If the fire system has a logging function check the fire panel log for output status information See Table 4 for information regarding 0 to 20 mA output 5 Turn off the input power to the detector and check all wiring for continuity Important Disconnect wiring at the detector before checking system wiring for continuity 6 If all wiring checks out and cleani...

Page 17: ...plate following the procedure described below oi PLATE REMOVAL 1 Disable any extinguishing equipment that is connected to the unit 2 Loosen the two captive screws then grasp the oi plate by the visor and remove it from the detector See Figure 17 3 Thoroughly clean the oi plate reflective surfaces holding it by its edges to avoid leaving fingerprints on the inside reflective surface 4 Re install th...

Page 18: ...at 24 Vdc in alarm 2 8 watts at 30 Vdc nominal 5 1 watts at 30 Vdc in alarm Total power 7 6 watts at 30 Vdc with EOL resistor installed EOL resistor must be ceramic wirewound type rated 5 watts minimum with actual power dissipation not to exceed 2 5 watts For HART model refer to Addendum number 95 8638 POWER UP TIME Fault indication clears after 0 5 second device is ready to indicate an alarm cond...

Page 19: ...ended Important 18 Vdc minimum must be available at the detector For ambient temperatures below 10 C and above 60 C use field wiring suitable for both minimum and maximum ambient temperature THREAD SIZE Conduit connection Four entries 3 4 inch NPT or M25 Conduit seal not required SHIPPING WEIGHT Approximate Aluminum 6 pounds 2 75 kilograms Stainless Steel 10 pounds 4 5 kilograms Swivel Mount AL 6 ...

Page 20: ...ble entry devices and blanking elements shall be certified to E generation or ATEX standards in type of explosion protection increased safety e or flameproof enclosure d as applicable suitable for the conditions of use and correctly installed They shall maintain the degree of ingress protection IP66 for the apparatus Unused apertures shall be closed with suitable blanking elements NOTE For ATEX in...

Page 21: ...01 1 oz grease for detectors non silicon 006097 001 Q1201 Laser 007240 001 Q1116A1001 Air Shield AL 007255 001 Q1201C1001 X Series Laser Holder AL Plastic 007290 001 Q9033B Stainless Steel Swivel Mount Assembly is for aluminum and stainless steel detectors 007290 002 Q9033A Aluminum Swivel Mount Assembly is for aluminum detectors only 007307 001 oi plate for X3301 requires inspector connector to c...

Page 22: ...E THREAD TYPE 4M 4 PORT METRIC M25 4N 4 PORT 3 4 NPT TYPE OUTPUTS 11 Relay 13 Relay and 4 20 mA 14 Eagle Quantum Premier EQP 15 Relay and Pulse 16 Addressable Module Only Third Party Type 23 HART Relay and 4 20 mA 24 Eagle Quantum TYPE APPROVAL AGENCY W FM CSA ATEX CE IECEx TYPE CLASSIFICATION 1 Division Zone Ex d e 2 Division Zone Ex d Detectors are always Class I Div 1 ...

Page 23: ...s a calibrated Automatic Optical Integrity oi test for each sensor Upon removal of the contamination the detector fault was cleared and the detector was verified to detect a fire The Manual Magnetic oi performs the same calibrated test as the Automatic oi and additionally actuates the alarm relay to verify output operation If there is a 50 loss of its detection range an alarm signal is not generat...

Page 24: ... unmodulated 3 0 9 1 x 1 foot n Heptane 75 22 9 1 300 w incandescent lamp modulated unmodulated 3 0 9 1 x 1 foot n Heptane 75 22 9 1 1500 w electric radiant heater modulated unmodulated 10 3 1 x 1 foot n Heptane 75 22 9 1 2 34 w fluorescent lamps modulated unmodulated 3 0 9 1 x 1 foot n Heptane 75 22 9 1 False Alarm Source Distance feet m Modulated Response Unmodulated Response Sunlight direct mod...

Page 25: ... 1 Standard n Heptane 1 x 1 foot 30 9 1 45 45 1 1 45 30 1 1 Hi Arc n Heptane 1 x 1 foot 30 9 1 45 45 2 2 45 30 2 2 Very Hi Arc Methane 32 inch plume 40 12 2 45 45 1 1 45 30 1 1 Standard Methane 32 inch plume 40 12 2 45 45 1 1 45 30 1 1 Hi Arc Methane 32 inch plume 35 10 7 45 45 1 1 45 30 1 1 Very Hi Arc Fuel Size Distance feet m Horizontal degrees Typical Response Time seconds Vertical degrees Typ...

Page 26: ...ch dia n Heptane 10 3 15 70 w sodium vapor lamp modulated unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 0 1 250 w vapor lamp modulated unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 0 1 300 w incandescent lamp modulated unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 0 1 500 w halogen lamp modulated unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 0 1 1500 w electric radiant heater modulated unmodulated 10 ...

Page 27: ...Sensitivity Standard Mode FM Approval and Performance Report Continued Fuel Size Distance feet m Horizontal degrees Typical Response Time seconds Vertical degrees Typical Response seconds Black Powder 40 grams 5 1 5 45 45 0 1 0 1 45 30 0 1 0 1 ...

Page 28: ...s Class I Division 1 Groups B C and D T5 Class II Division 1 Groups E F and G T5 Class I Division 2 Groups A B C and D T3 Class II Division 2 Groups F and G T3 Class III Enclosure Type 4X Ultraviolet Flame Detector Controller X2200 series rated 18 30 Vdc 2 5 Watts to 7 6 Watts Relay contacts rated 5 Amps 30 Vdc ...

Page 29: ... use with the terminal compartment in type of explosion protection flameproof enclosure d or in type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The metal ...

Page 30: ...ype of explosion protection flameproof enclosure d or in type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The metal housing for the Ultraviolet UV flame de...

Page 31: ... OF THE APPROVAL UV Flame Detector Type X2200 for use in Automatic Fire Detection and Fire Alarm Systems BASIS OF APPROVAL DIN EN 54 Part 10 05 02 Flame Detectors INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT SYSTEM The Installation shall take into account that the orientation arrow on the flame detector is directed upwards as the view angle in this direction is 90 The UV flame detect...

Page 32: ...ty oi are registered trademarks or trademarks of Detector Electronics Corporation in the United States other countries or both Other company product or service names may be trademarks or service marks of others Copyright Detector Electronics Corporation 2010 All rights reserved 95 8549 X3301 Multispectrum IR Flame Detector PointWatch Eclipse IR Combustible Gas Detector Eagle Quantum Premier Safety...

Reviews: