background image

3.1

95-8452

3

MOUNTINg ThE DETECTOR

Using three No. 8 flat head screws placed through 

1. 

the  counterbored  holes  in  the  detector  flange, 

secure the detector to the surface location.  Secure 

the junction box if necessary.
Remove  the  cover  from  the  junction  box  and 

2. 

complete  installation  of  system  conduit.    Feed  the 

external wiring through the remaining junction box 

entry or M25 to 3/4 inch adapter.  Use care not to 

damage the wires by twisting them when installing 

the junction box.
Connect  the  external  wiring  to  the  appropriate 

3. 

terminals and re-install the junction box cover.  See 

Figures 3, 4 and 5 for wiring details.

DETECTOR CONNECTIONS

The U5005 contains two sets of relay contacts:

One set of NO Alarm contacts close upon detection 

1. 

of smoke.
One  set  of  NC  Trouble  contacts  close  when  the 

2. 

detector is powered.

3.5 (8.9)

14.4 (36.6)

B1967

120°

5/32 INCH DIA. (3)

2.4 (6.1)

5.3 (13.5)

3.46

(8.8)

4.7

(11.9)

2.7

(6.9)

5.2

(13.2)

5.86

(14.9)

3.77

(9.6)

1.28

(3.3)

Figure 2—U5005 Dimensions in Inches (Centimeters)

1

2

3

4

5

NORMALLY CLOSED SUPERVISORY CONTACTS

NORMALLY OPEN ALARM CONTACTS

                 AUXILIARY ALARM CONTACTS

+

GROUND

YELLOW
YELLOW
VIOLET
VIOLET
BLACK
RED

TO DETECTOR

1        2        3       4        5        6

TB – 1

TB – 2

TB – 3

NOTE:

CIRCUIT SHOWN IN THE NORMAL STANDBY ENERGIZED MODE

C1192

7

10

8

9

6

Figure 3—wiring Terminals

Summary of Contents for DET-TRONICS U5005

Page 1: ...taic smoke cell which is placed at an angle to the pulsed invisible light source is sensitive to the infrared light in the specified frequency emitted by the IRED light source and is designed to receive a signal only when the pulsed IRED source is activated See Figure 1 When smoke enters the chamber the light from the IRED reflects off the smoke particles and reaches the photovoltaic smoke cell Wh...

Page 2: ...in the event of an alarm and an LED located on the outer surface of the housing is illuminated to provide a visual indication that an alarm condition has occurred The detector is reset by momentarily interrupting input power SPECIFICATIONS OPERATING VOLTAGE 20 to 28 Vdc filtered supply with less than 1 4 vpp at 60 to 120 Hz OPERATING CURRENT Standby 10 milliamperes Alarm 35 milliamperes TEMPERATUR...

Page 3: ...ls and re install the junction box cover See Figures 3 4 and 5 for wiring details Detector Connections The U5005 contains two sets of relay contacts One set of NO Alarm contacts close upon detection 1 of smoke One set of NC Trouble contacts close when the 2 detector is powered 3 5 8 9 14 4 36 6 B1967 120 5 32 INCH DIA 3 2 4 6 1 5 3 13 5 3 46 8 8 4 7 11 9 2 7 6 9 5 2 13 2 5 86 14 9 3 77 9 6 1 28 3 ...

Page 4: ...B 3 POWER 2 WIRE CLASS B RECEIVING ZONE CHASSIS GROUND LISTED CONTROL PANEL EOL DEVICE SUPPLIED BY PANEL MANUFACTURER ADD JUMPER GROUND STUD B1193 6 7 8 9 10 Figure 4 Single Detector Wiring Figure 5 Multiple Detector Wiring FIRST DETECTOR IN LOOP TB 2 LAST DETECTOR IN LOOP TB 2 TB 3 POWER 2 WIRE CLASS B RECEIVING ZONE CHASSIS GROUND LISTED CONTROL PANEL AUXILIARY ALARM CONTACTS C NO NC AUXILIARY A...

Reviews: