b-2
95-8618
4.3
UD10 Wired to GT3000 Detector with Sensor Termination box
NOTE 1
GROUND THE SHIELD AT THE DISPLAY
UNIT END ONLY.
NOTE 2
HOUSINGS MUST BE ELECTRICALLY
CONNECTED TO EARTH GROUND.
SEE NOTE 1
UD10 DISPLAY UNIT
C2401
RED
BLACK
GT3000
GAS DETECTOR
SENSOR TERMINATION BOX
Sensor Connector
Power Supply Connector
Output Loop
Connector
MODBUS
Connector
R
ela
y Connect
or
P1
J2
J3
J4
P2
4-20 mA +
4-20 mA –
SHIELD
COM
RS485 A
RS485 B
HIGH ALARM COM
HIGH ALARM NC
HIGH ALARM NO
AUX ALARM COM
AUX ALARM NC
AUX ALARM NO
LOW ALARM COM
LOW ALARM NC
LOW ALARM NO
FAULT COM
FAULT NC
FAULT NO
24
VDC –
24
VDC +
SHIELD
24
VDC –
24
VDC +
SHIELD
SHIELD
C
ALIBR
A
TE
24
VDC –
4-20 mA
24
VDC +
P1-3
P1-2
P1-1
J2-3
J2-2
J2-1
J4-1
J4-2
J4-3
J4-4
J4-5
J4-6
J4-7
J4-8
J4-9
J4-10
J4-11
J4-12
J3-1
J3-2
J3-3
J3-4
J3-5
P2-6
P2-5
P2-4
P2-3
P2-2
P2-1
RED
RED
BLA
CK
BLACK
GREEN
orientAtion
The device must be mounted in a vertical position only,
with the GT3000 pointing down.
liVe mAintenAnce
noTe
The sensor module on the GT3000 Gas Detector
can be hot swapped, i.e. replaced without
removing power or de-classifying the area. To
replace a GTX Transmitter connected to the UD10
with a new transmitter or a different detector type,
the area
must
be de-classified.
noTe
Removing the sensor module with power applied
will result in a fault condition until a new sensor
module of the same type is installed. When
replacing an oxygen sensor, this action will also
result in an alarm condition as the decreasing
4-20 mA signal passes through the alarm range.
Inhibit response devices to prevent unwanted
actuation.
For complete information regarding sensor replacement
with the GT3000 Gas Detector, refer to the GT3000
instruction manual number 95-8616.