Page 9
The yellow wire is used only for multiple station operations with USI ELECTRIC or UNIVERSAL
Model alarms only. Connecting this yellow wire to any other circuits may result in damage
and alarm malfunction. When alarms are interconnected, all alarms must be powered from a
single AC branch circuit. If local codes do not permit, be sure the neutral wire is common to
both phases. The maximum wire run distance between the first and last alarm/device in an
interconnected system is 1,000 feet. NOTE: Use standard household wire (18 gauge or larger,
rated at least 300V, as required by local codes) available at all electrical supply/hardware
stores. The wiring to be used shall be in accordance with the provisions of Articles 210 and
300.3(B) of the National Electrical Code, ANSI/NFPA 70. In addition, the resistance of the
interconnecting wiring shall be a maximum of 10 Ohms.
2.
Attach the mounting bracket to the electrical junction box.
3.
To activate 9 volt battery and alarm, hold the QUICK DRAW
(R)
battery drawer closed, pull and
remove the PULL-TAB. Confirm that the entire PULL-TAB has been completely removed. Discard
PULL-TAB.
4.
Plug the AC QUICK CONNECTOR into the alarm base. Push and twist the alarm clockwise
onto the mounting bracket.
5.
See "OPTIONAL TAMPER RESISTANT FEATURES" and "TO ACTIVATE THE LOCKING
FEATURES" instructions on Page 4.
6.
Turn on AC power and check the LED's for proper operation. The green LED should be on to indicate
AC power. The red LED blinks on once approx. every 40 seconds to indicate proper operation.
IMPORTANT!
The battery backup is designed to provide short-term emergency power to the Smoke, CO and Gas
Alarm. Actual backup time depends on the strength (freshness) of the battery. The battery backup
will not work unless a good battery is properly installed.
When the alarm utilizes battery backup power, the natural gas sensor will operate the alarm and will
sample less frequently to extend battery life. Natural gas could be present during this period between
samples without the alarm sounding, especially if there is a rapid buildup of natural gas.
NOTE: It is best to “reset” the alarms before initial test is performed. See Page 10 for Reset procedures.
OPERATION, TESTING & MAINTENANCE
OPERATION:
The alarm is operating once the AC power is connected and turned on. When products
of combustion are sensed, the alarm sounds a loud alarm which continues until the air is cleared.
This alarm incorporates the NFPA recognized horn signal for evacuation. During smoke alarm mode,
the horn produces three beeps followed by a two second pause and then continually repeats.
READY/ACTIVE CONDITION:
The green LED is on and blinks off once approx. every 20 seconds
to indicate the alarm is properly functioning.
LOCAL ORIGINATING SMOKE ALARM CONDITION:
The green LED turns off and the red LED
blinks on approx. every second while the alarm emits a loud, pulsating alarm sound.
NON-ORIGINATING SMOKE ALARM CONDITION:
The red LED is off and the alarm emits a loud,
pulsating alarm.
GREEN LED:
The green LED is off and blinks on approx. every 40 seconds whenever AC power is
turned off.
CO ALARM:
The alarm signal is 4 beeps, 5 second pause, repeat. The red LED blinks on in sync
with the cycle of 4 beeps.
GAS ALARM:
The alarm signal is 1 beep, 2 second pause, repeat. The blue LED blinks on in sync
with the horn beep every second.
120 VAC 60Hz
100mA Max.