US Water Systems 200-RODI4 series Installation And Maintenance Manual Download Page 5

Installation Instructions 

Reverse Osmosis/Deionization Water System 

Page 5 

Maintenance 

The RO/DI system contains filters and membranes which must 
be replaced periodically for proper operation.  
 

NOTE:  Change-out  frequencies  may  vary,  depending  on 
feed water conditions. 

 
The  Reverse  Osmosis/Deionization  System  has  been  tested 
to  ensure  it  will  operate  correctly.  The  following  periodic 
maintenance  is  recommended  so  the  system  will  provide 
years of trouble-free service: 
 

 

 
To change filters and membranes follow these procedures: 
1.  Close feed water valve. 
2.  Open  the  product  line  and  allow  the  system  to 

depressurize.   

3.  Loosen and remove filter housings using wrench provided 

and discard cartridges and/or membrane. 

4.  Wash the inside of the housings using mild detergent and 

soft cloth. Thoroughly rinse all soap before reassembly. 

5.  Replace  filter  cartridges  and  membrane  (if  necessary) 

after sanitizing system. 

 

Sanitizing instructions 

To sanitize system follow these procedures with the feed 
water valve closed and system de-pressurized.   
1.  Remove pre-filters and membrane from housings. 
2.  Use 5-1/4% unscented bleach such as Clorox or an 

approved sanitizing solution. 

3.  Add one cap full (2 tsp. or 10 ml) of bleach to each pre 

and post filter housing and membrane module. 

4.  Carefully re-fill housings with tap water and 

temporarily replace 

WITHOUT 

carbon cartridge, 

sediment cartridge, membrane or DI cartridge 
installed. 

5.  Slowly open the feed water line and product water line 

from the system. 

6.  Close the product line when water begins to come out 

of the system and has a strong chlorine smell.  The 
system should shutoff when it pressurizes. 

7.  Let system stand for approximately 30-60 minutes. 
8.  After the minimum of 30 minutes perform the following 

steps; 

9.  Open the product line and allow the system to flush until 

the chlorine smell is gone.   

10.  Close feed water valve and leave the product line open. 
11.  Allow the system to de-pressurize. 
12.  Remove housings and empty the water. 
13.  Remove any protective wrap from pre-filters and 

membrane and install them in the appropriate filter 
housings. NOTE: 

Be sure to check that the O-rings 

are in place when installing cartridges in filter 
housings. 

Tighten the housings hand tight and the 

sumps on the bottom can be tightened an additional 
1/2-3/4 turn with supplied wrench. 

14. 

Slowly open feed water valve. When water begins to 
drip from the product line, allow it to run until the 
proper quality is being produced from the system. 
(See System Startup)

 

Water quality 

Water  quality  from  an  RO/DI  system  is  normally  determined 
with  a  TDS  Meter,  Conductivity  Meter  or  Resistivity  Meter, 
which  measures  total  dissolved  solids,  conductivity  or 
resistivity of the water.  
RO  membranes  are  rated  by  the  amount  of  dissolved  solids 
they reject expressed as “rejection percentage”. 

Note: The membrane must be checked with a TDS meter.  
Conductivity or Resistivity is not a good way to determine 
membrane  quality.    Check  the  membrane  at  the  DI 
Cartridge Inlet Tubing.

 

For example: 
If the feed water contains 100 ppm of dissolved solids and the 
product water after the membrane (before the DI filter) tests at 
10  ppm  of  dissolved  solids  the  rejection  rate  is  90%.    This 
membrane  efficiency  must  be  checked  on  the  inlet  to  the  DI 
cartridge to ensure the membrane is being checked and that 
the DI cartridge isn’t giving a false reading.  This is only for the 
membrane  performance  and  no  the  DI  cartridge.  The  DI 
cartridge should be checked using the meter that reflects the 
specified water quality units.   
The formula is as follows: 

RO membranes should operate between an 80-97% rejection 
rate.  Once the rejection falls below 80%, the membrane must 
be replaced.  

Replacement part

 

Frequency

 

Pre-filter (sediment)

 

Every 6-12 months

 

Pre-filter (activated carbon)

 

Every 6-12 months

 

R/O membrane

 

Every 3-5 years

 

DI Cartridge

 

As needed

 

Percent Rejection 

(Feed H

2

O TDS - Product H

2

O TDS) x 100% 

Feed H

2

O

 

 

Summary of Contents for 200-RODI4 series

Page 1: ...nd Maintenance Manual US Water Systems 1209 Country Club Road Indianapolis IN 46234 1 800 608 8792 www uswatersystems com US Water 4 Stage RO DI System REVISION 1 0 5 12 2015 Owners Manual Models 200...

Page 2: ...ve ASO PRE FILTER sediment filter removes larger particles such as sand silt rust and scale activated carbon filters re move chlorine in the feed water to protect the reverse osmosis membrane REVERSE...

Page 3: ...ure the membrane is fully seated in the housing This can be done by pushing on the center pipe in the membrane with the thumb There are two O rings on the membrane center pipe that must be seated in t...

Page 4: ...valve and allow the system to run until there is no air in the water stream 2 Close product water valve and re fill the system 3 Allow system to process water until the tank is full or the system is p...

Page 5: ...feed water valve and leave the product line open 11 Allow the system to de pressurize 12 Remove housings and empty the water 13 Remove any protective wrap from pre filters and membrane and install the...

Page 6: ...ditions of 77 F 25 C and 60 psi 4 bar discharging to atmosphere These factors should be considered when sizing RO systems for a particular application Every degree of temperature below 77 F will reduc...

Page 7: ...site and or before use Disconnecting Push in Collet and remove tube To disconnect ensure the system is depressurized before removing the tube Push in collet squarely against face of fitting With the c...

Page 8: ...Installation Instructions Reverse Osmosis Deionization Water System Page 8...

Page 9: ...Installation Instructions Reverse Osmosis Deionization Water System Page 9...

Page 10: ...Installation Instructions Reverse Osmosis Deionization Water System Page 10...

Page 11: ...HE TERMS OF THIS EXPRESSED WARRANTY AND THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THOSE HEREIN US WATER SYSTEMS INC SHALL NOT BE LIABLE WHATSOEVER FOR ANY INCIDENTIAL AND OR CONSEQUENTIAL DAMAGES SO...

Reviews: