UC1122 User Guide
21
The user is also able to specify a "Continued time" for this command, which will not be triggered
until it remains Active or Inactive longer than the time specified. Moreover, the user can specify a
"Lockout time" for this command. After the command has been triggered, it will not be allowed
to be triggered again until the time specified has elapsed.
When you set the time, you can choose the time unit:
Msec: 0-86400000
sec: 0-86400
min: 0-1440
Only integers are allowed. You can't use the decimal point.
Note
: There are 3 single actions at most to be executed for a single trigger condition.
4.6.1.4 IF Analog Input
A statement containing this IF condition will be triggered if the analog voltage measured at the
terminals meets the specified requirements.
Then the user can choose from the following options:
•
above
•
below
•
within
Thus, if the user chooses
, then as soon as the value of this
analog input goes above the specified threshold, the statement will be triggered.
Thus, if the user chooses
, then as soon as the value of this
analog input goes below the specified threshold, the statement will be triggered.
Thus, if the user chooses
, then as soon
as the value of this analog input goes within the specified threshold, the statement will be
triggered.