background image

04

Discharge over current protection 1 

110±5A, delay 4~6min

Over current

Discharge over current protection 2

300±20A, delay 5~6s 

Over current release method

8s after cutoff the load

Battery 
temperature

Charge over temperature 

Protection @55±5°C

Discharge over temperature

Release @55±5°C

Protection @65±5°C

Release @45±5°C

Short

Do not short-circuit the electrodes

5s after cutoff the load

Over-discharge protection for each cell

2.80±0.04V

Over discharge

Over-discharge release for each cell

3.00±0.04V

Over-discharge release method

Charging recovery

UE-36Li100

5. Protective Circuit Specification

The batteries are supplied with a LiFePO4 Battery Management System (BMS) that can monitor and optimized 
each single prismatic cell during charge & discharge, to protect the battery pack overcharge, over discharge, 
short circuit. Overall, the BMS helps to ensure safe and accurate running.

Items

Over-charge protection for each cell

Specification

Content

3.75±0.03V

Over charge

Over-charge release for each cell

3.60±0.05V

Over-charge release method

Under the release voltage

Static power

≤200uA

www.upowerbatteries.com

66A Tzar Asen Srt.
Sofia, Republic of Bulgary
Tel. (+34) 918 021 649
Fax. (+34) 917 750 542
[email protected]

Summary of Contents for Ecoline UE-36Li100

Page 1: ...f the battery pack NO Items Criteria 100Ah 98Ah 3 84KWh Rated Capacity Minimum Capacity Energy Floating charge voltage Internal resistance Limited charge voltage 38 4V 38 4V 41 4 0 2V 2 3 4 5 6 7 Nomi...

Page 2: ...3 1 1 Unless otherwise specified all performance tests is required conducted at temperature 25 C 2 C Humidity less than 45 75 RH 3 1 2 Unless otherwise specified the tested product is required unused...

Page 3: ...an t discharge and then rest it for 1h Charge the battery following CC 1C CV 43 8V mode to full capacity and then rest it for 1h Repeat above process until full charged capacity is no more than 80 of...

Page 4: ...ischarge release method Charging recovery UE 36Li100 5 Protective Circuit Specification The batteries are supplied with a LiFePO4 Battery Management System BMS that can monitor and optimized each sing...

Page 5: ...tayed in the warehouse 15 C 35 C where it s dry clean shade and well ventilated The battery should be stored in 50 SOC during transportation The battery need to be charged every 6 months if out of use...

Page 6: ...stop using and take it out from device If the battery leaks and get into the eyes or skin do not wipe instead rinse it with clean water and see doctor immediately Please far away from children or pet...

Page 7: ...not maintained within the specified ranges the life expectancy of the battery may be shortened or the device in which the battery is used may be damaged by electrolyte leakage If the discharge time is...