48V100Ah - Energy Storage Lithium Battery Module - User Manual
RS485 terminal: (RJ45 port) the RS485 terminal outputs battery information. The default baud rate is 9600 bps. When
batteries are deployed in parallel, you need to set the address of each battery using a dip switch.
RS485
Pin Number
Foot 1 and Foot 8
Foot 2 and Foot 7
Foot 3 and Foot 6
Foot 4 and Foot 5
Function Definition
RS485-B
RS485-A
NC
NC
Pin Definitions of the RS485 Port
If battery strings are connected in parallel and need to communicate in cascading mode, the hardware address of each
battery must be configured. The hardware address can be set using the dip switch on the board. When the batteries are
in parallel, address 1 is the host and other addresses are slave.
The battery at address 1 is connected to the inverter; If the address is 0,
it is in single-battery mode
For details about the switch, see the following table.
ADD Switch
1
2
3
4
ON
OFF
Battery Address Definition
Address
Switch Position
1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
PACK 0
PACK 1
PACK 2
PACK 3
PACK 4
PACK 5
PACK 6
PACK 7
PACK 8
PACK 9
PACK 10
PACK 11
PACK 12
PACK 13
PACK 14
PACK 15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON