Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 23
Display name
Register
address
(decimal)
Function code
(Hex)
Type
Analogue/
Binary
Coding
Floor temperature data channel 1
30026
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 2
30027
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 3
30028
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 4
30029
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 5
30030
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 6
30031
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 7
30032
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 8
30033
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 9
30034
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 10
30035
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 11
30036
0x04
Read
Analogue Signed 16 bit integer.
Floor temperature data channel 12
30037
0x04
Read
Analogue Signed 16 bit integer.
Thermostat loss
30038
0x04
Read
Binary
Unsigned.
1 = Thermostat loss, 0 = No alarm.
Dynamic heat curve offset in
integrated heat pump
*
30039
0x04
Read
Analogue
Signed 16 bit integer.
Absolute degree value (-10 to +10)
+10 = 000A
+1 = 0001
0 = 0000
-1 = 00FF
-10 = 00F6
* Requires
Heat Pump Integration via BMS to be activated in U_BMS.txt.