Uponor Smatrix Base PRO X-147 Installation Manual Download Page 1

Uponor Smatrix Base PRO Controller X-147 

 Modbus RTU interface

EN

Installation manual

Summary of Contents for Smatrix Base PRO X-147

Page 1: ...Uponor Smatrix Base PRO Controller X 147 Modbus RTU interface EN Installation manual...

Page 2: ...Heating Cooling state Heating Cooling offset Comfort ECO Autobalancing on off Cooling not allowed for a room Comfort setting Integrated heat pump defrost state Requires Heat Pump Integration via BMS...

Page 3: ...ilable settings default in bold BMS Slave address 1 to 247 BMS Baud rate 19200 or 9600 BMS Parity even odd or no Heat pump integration via BMS off or on on enables dynamic heat curve offset in integra...

Page 4: ...o the Base PRO controller system device bus Study the wiring diagrams of the controller to locate the connector position Caution Depending of EMC conditions in the installation and or distance between...

Page 5: ...RS232 RS485 X101 X300 I 147 X 147 230 V AC BMS T 141 T 143 T 144 T 145 T 146 T 147 T 148 T 149 PRO PRO Beckhoff Modbus RTU X300 A B 24V 0V L N 230 V AC RxD RxD TxD TxD Caution If an Uponor Smatrix Bas...

Page 6: ...0x01 Starting register address 0x0000 0xFFFF Number of coils to read 1 2000 CRC 1 byte 1 byte 2 bytes 2 bytes 2 bytes Response Slave address 0x01 0xF7 Function code 0x01 Byte count N Coil status n N...

Page 7: ...ple Read all discrete inputs Slave address 0x01 Function code 0x02 Byte count 0x02 Coil status 1 to 8 0xAA Coil status 9 to 16 0x0A CRC 1 byte 1 byte 2 byte 1 bytes 1 bytes 2 bytes Request example Rea...

Page 8: ...read HI 0x00 Quantity of holding registers to read LO 12 channels 0x0C CRC 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 bytes Response example Read setpoints 21 0 C 69 8 F value 689 0x02BA 12 channels...

Page 9: ...01 Function code 0x03 Byte count 0x02 Holding register HI 0x00 Holding register LO Off 0x00 CRC 1 byte 1 byte 1 byte 1 bytes 1 bytes 2 bytes Request example Read heating cooling offset temperature Sla...

Page 10: ...e 1 byte 1 byte 1 byte 1 byte 1 byte 2 bytes Response example Read room temperature data 21 0 C 69 8 F value 689 0x02BA for all zones Slave address 0x01 Function code 0x04 Byte count 0x18 Input regist...

Page 11: ...dress HI 0x00 Starting register address LO Start at 38 0x25 Quantity of input registers to read HI 0x00 Quantity of input registers to read LO 0x01 CRC 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 byte...

Page 12: ...ase of error Slave address 0x01 0xF7 Error code 0x85 Exception code 01 02 03 04 or 06 CRC 1 byte 1 byte 1 byte 2 bytes Example Request example Change state from ECO to Comfort Slave address 0x01 Funct...

Page 13: ...0x02 Register value LO 0xDE CRC 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 bytes Response example Write 23 C 73 4 F value 734 0x02DE setpoint channel 5 Slave address 0x01 Function code 0x06 Output ad...

Page 14: ...Output value written HI 0x00 Output value written LO 0x0C CRC 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 bytes Request example Write 5 C 41 0 F value 410 0x005A heating cooling offset temperature Sla...

Page 15: ...in case of error Slave address 0x01 0xF7 Error code 0x8F Exception code 01 02 03 04 or 06 CRC 1 byte 1 byte 1 byte 2 bytes Example Request example Changes states to Cooling and ECO Slave address 0x01...

Page 16: ...xample Write 23 C 73 4 F value 734 0x02DE maximum setpoint limit and 18 C 64 4 F value 644 0x0284 minimum setpoint limit channel 5 Slave address 0x01 Function code 0x10 Starting register address HI 0x...

Page 17: ...Data value Hex value 40 0 40 0 400 0xFE70 30 0 22 0 220 0xFF24 20 0 4 0 40 0xFFD8 17 8 0 0 0 0x0 10 0 14 0 140 0x8C 5 0 23 0 230 0xE6 0 0 32 0 320 0x140 1 0 33 8 338 0x152 5 0 41 0 410 0x19A 10 0 50 0...

Page 18: ...n set a basic level of comfort for a zone when there is no demand for heating The value set is the percentage of time the actuators are opened It will shorten the heat up time for the room which is us...

Page 19: ...oling not allowed 1 Cooling allowed default 0x05 Write 0x0F Write multiple Cooling not allowed channel 3 00006 0x01 Read Binary Unsigned 0 Cooling not allowed 1 Cooling allowed default 0x05 Write 0x0F...

Page 20: ...ad Binary Unsigned 0 Cooling not allowed 1 Cooling allowed default 0x05 Write 0x0F Write multiple Cooling not allowed channel 12 00015 0x01 Read Binary Unsigned 0 Cooling not allowed 1 Cooling allowed...

Page 21: ...0x02 Read Binary Unsigned 1 ON 0 Off Actuator status channel 5 bit 4 10005 0x02 Read Binary Unsigned 1 ON 0 Off Actuator status channel 6 bit 5 10006 0x02 Read Binary Unsigned 1 ON 0 Off Actuator sta...

Page 22: ...16 bit integer Room temperature data channel 10 30011 0x04 Read Analogue Signed 16 bit integer Room temperature data channel 11 30012 0x04 Read Analogue Signed 16 bit integer Room temperature data cha...

Page 23: ...nalogue Signed 16 bit integer Floor temperature data channel 7 30032 0x04 Read Analogue Signed 16 bit integer Floor temperature data channel 8 30033 0x04 Read Analogue Signed 16 bit integer Floor temp...

Page 24: ...rite multiple Room setpoint temperature channel 5 40005 0x03 Read Analogue Signed 16 bit integer Range min max temperature default 21 C 69 8 F 0x06 Write 0x10 Write multiple Room setpoint temperature...

Page 25: ...efault 35 C 95 F 0x10 Write multiple Room setpoint min temperature channel 5 40022 0x06 Write Analogue Signed 16 bit integer Range 5 max temperature default 5 C 41 F 0x10 Write multiple Room setpoint...

Page 26: ...ltiple Room floor min limit temperature channel 3 40042 0x06 Write Analogue Signed 16 bit integer Range 10 30 or max temperature default 20 C 68 F 0x10 Write multiple Room floor max limit temperature...

Page 27: ...or min limit temperature channel 12 40060 0x06 Write Analogue Signed 16 bit integer Range 10 30 or max temperature default 20 C 68 F 0x10 Write multiple Comfort setting channel 1 40061 0x03 Read Analo...

Page 28: ...el 11 40071 0x03 Read Analogue Signed 16 bit integer Range 0 off 5 12 5 12 default 0 0x06 Write 0x10 Write multiple Comfort setting channel 12 40072 0x03 Read Analogue Signed 16 bit integer Range 0 of...

Page 29: ...t file correctly See section 1 2 Preparation step 3 for more information Incorrect software version in the controller Install the correct software in the controller See section 1 2 Preparation step 2...

Page 30: ...t Germany Uponor reserves the right to make changes without prior notification to the specification of incorporated components in line with its policy of continuous improvement and development www upo...

Reviews: