7.10 Pipe clip sensor safety
temperature monitor (STW)
Before the secondary heating supply is connected, the pipe clip
sensor safety temperature monitor (STW) prevents excessive
temperatures and provides an emergency-off function for the radiant
heating circuit.
A
B
CD0000268
Item
Description
A
Contact sensor
B
Safety temperature monitor
•
Open the response temperature:
55 °C +/- 3 K
•
Close the reset:
45 °C +/- 4 K
•
Use an oil flex cable
110 mm, 2 x 0.75 mm²
, length
1000 mm
for fastening and mounting on the pipeline.
•
Use supply cable ends with ferrules.
7.11 Cold water throttle disc
Note
The installed cold water throttle disc can be replaced by
a corresponding throttle disc if required (see table
below). The colour indicates the maximum inserted
volume flow.
A cold water throttle disc is located in the connection between the
cold water connection of the volume control valve and the strainer.
The throttle disc limits the amount of cold water to the heat
exchanger and prevents the hot water supply from exceeding the
calculated volume.
Flow regulator insert colour
l/min
Black
6
White
8
Orange
9
Blue
10
Red
12
Green
15
Brown
17
Black
19
Purple
22
Replacing the throttle disc
Note
Observe the flow direction when replacing the throttle
disc!
CD0000258
A
B
C
B
Item
Description
A
Strainer
B
Throttle disc
C
Retaining ring
1.
Dismantle the strainer.
2.
Dismantle the retaining ring. Use special pliers for this.
3.
Replace the throttle disc in accordance with the desired setting
value.
4.
Fix the retaining ring.
5.
Fix the strainer.
7.12 Hydraulic balancing on the
manifold
Warning!
The pressure in the valves can cause personal injury.
Caution!
Never turn the valves counter clockwise more than five
(5) turns. When the cap is completely unscrewed, the
valves will shoot out of the thread.
CLOSE
OPEN
0.25 x
1
2
3
4
CD0000301
1.5
l/min
5
1.
Remove the cap from the fill/flush valve on the return manifold
bar. Turn it around until the square connector is down.
2.
Close the valve.
3.
Open the regulation valve
0.25 x
4.
Adjust the regulation valve as many turns as necessary to
achieve desired loop setting.
5.
Consider the planning documentation when adjusting the flow
rate on the relevant top meter.
Combi Port Base
|
Installation and operation manual
|
21