15
Position the bottom of the 2550 enclosure where it will be installed. Use four (4)
#6 screws and mount the unit using the four holes in the enclosure’s plastic
bottom. The 2550 unit’s dimensions are shown in Figure 2.
Figure 2: Inside & Outside Mounting Dimensions for the 2550
5. Make sure the unit’s antenna is connected, then place the backup battery in
its location in the bottom of the plastic enclosure.
6. Connect the positive (+) and negative (-) terminals of the battery to terminals
13 (BAT+) and 14 (BAT -) respectively on the 2550 JP10 terminal strip.
7. Connect the wires from the 120 to 16.5 VAC, 40 VA transformer to terminal
strip positions 11 and 12 (designated as “AC”) on the unit’s JP10 terminal
strip. Plug the transformer into a 120 VAC non-switched outlet. Use 18 to 14
gauge wire for wire lengths of 10 to 25 feet respectively. For wire lengths
longer than 25 feet, contact Uplink Technical Support.
8. Double check to make sure that the RSSI is still showing a good signal
strength level.
9. Before connecting the alarm panel and the 2550, first:
a. Return Dipswitch #4 (S4) to the OFF position.
b. Disconnect the AC transformer from its power outlet.