background image

 

 
Item No. 0BL-00-010            Rev. 12/21/2017           Copyright (C) 2017, Universal Metal Industries, Inc.         Prov. 22:29         Page 10 

Best Practices 

Venting Installation Instructions 

Addendum to Installation 

Instructions 

Model:  S7200CD Series

 

 

 

IMPORTANT:  

Problems caused by improper installations are not covered by the manufacturer’s warranty.  

 
IMPORTANT:  

Undersized and improperly installed duct pipe and/or other ventilation components will cause excessive static 

pressure (air resistance), that may result in rattling, vibration and air buffeting noises, as well as inadequate ventilation. 

 

1.

 

Building Codes 

BBQ Hood Ventilators should be installed by qualified technicians familiar with state and local building codes. 
 

2.

 

Duct Pipe and Fittings (Elbows, Transitions, Roof & Wall Caps)  

a.

 

Use round or rectangular rigid metal duct only.  Where possible, use round duct as it creates the least amount of 

static pressure.  DO NOT use flex duct. 
 

b.

 

All duct sections and fittings (EXCEPT DAMPERS, per Section 4), should overlap and be connected with at least 3 – 4 
equally spaced screws and wrapped tightly with 2 – 3 layers of Aluminum Foil Metal Duct Tape.  This type of duct 
tape is more durable than traditional cloth duct tape.  DO NOT use butt joints. 
 

c.

 

For best air flow, elbows and pipe size transition fittings should not be directly connected to one another.  Where 

possible, always include at least 15 inches of straight pipe between fittings. 
 

3.

 

Duct Pipe and Fitting Sizes 
IMPORTANT:  

No portion of any length of duct pipe or fitting should be smaller than the discharge port of the ventilator.  

This is very important because any type of restriction anywhere in the ventilation system will cause increased static 
pressure (air resistance), that may result in rattling, vibration and air buffeting noises, as well as inadequate ventilation.  

See 

Duct Sizing Chart and Area Calculations 

section for more detail. 

 

Duct Runs – Length 

a.

 

Configure the ventilation duct run to be as short and as direct to the outside as possible.  Minimize the number of 
elbows and transition fittings used.  Complex or long runs should be reviewed by a qualified installer. 
 

b.

 

No portion of the ducting should be run so that the exhaust air flows downward.  Since exhaust heat rises, forcing 
the air to flow downward will cause increased static pressure.  As previously mentioned, improperly installed duct 

pipe will cause excessive static pressure (air resistance), that may result in rattling, vibration and air buffeting noises, 
as well as inadequate ventilation. 
 

c.

 

Duct runs for 1200CFM ventilator models should not exceed 35 linear feet with two 90-degree elbows and two 45-
degree elbows, a damper and a roof or wall cap.  Longer runs or additional elbows will result in decreased 
ventilation performance.  Each 90-degree elbow is the equivalent of 6 linear feet of duct pipe; each 45-degree elbow 
is equivalent to 3 linear feet of duct pipe. 

 

d.

 

Always run ventilator ducts to the outdoors.  DO NOT terminate a duct into an attic, basement, garage, crawl space 
under a house, a chimney, other ducting or an enclosed room. 
 

4.

 

Dampers

 

 IMPORTANT:

  DO NOT USE ANY TYPE OF DAMPER IN A BBQ HOOD APPLICATION. 

 
In ventilation systems utilizing a roof cap or wall cap 

with

 a built-in damper, remove it. Dampers are unnecessary and will 

cause increased static pressure (air resistance), that may result in rattling, vibration and air buffeting noises, as well as 
inadequate ventilation.

 

Summary of Contents for Trade-Wind S723612CD

Page 1: ...coverage on all sides that are not protected from direct rain by an adjacent wall It is required that all duct work and roof openings be thoroughly sealed with the applicable tape and or roof sealant...

Page 2: ...T b NEVER PICK UP A FLAMING PAN YOU MAY BE BURNED c DO NOT USE WATER including wet dishclothes or towels a violent steam explosion will result d Use an extinguisher ONLY if 1 You know you have a Class...

Page 3: ...sides that are not protected from direct rain by an adjacent wall g It is also required that all duct work and roof openings be thoroughly sealed with the applicable tape and or roof sealant to preven...

Page 4: ...scharge configuration default See page 6 for dimensions relating to rear discharge option IMPORTANT All dimensions are nominal 1 8 FRONTVIEW FRONTVIEW Model No Blower 1200 CFM S7236CD S723612CD S7242C...

Page 5: ...off the 8 nuts and washers to release the other solid plate currently mounted inside the back of the unit Put in place where the other plate was top of unit and secure using same nuts and washers 6 No...

Page 6: ...wings below show rear discharge configuration after easy conversion IMPORTANT All dimensions are nominal 1 8 BACKVIEW BACKVIEW Model No Blower 1200 CFM S7236CD S723612CD S7242CD S724212CD S7248CD S724...

Page 7: ...Follow instructions carefully to ensure proper installation It is the owner s responsibility to ensure that a qualified person performs the electrical connection of this appliance The electrical inst...

Page 8: ...n performance and appearance while also ensuring safe operation The frequency of cleaning should be adjusted according to the type and amount of cooking Best results will be achieved by cleaning soile...

Page 9: ...es or reset breakers Service calls to correct faulty installation such as performance issues relating to improperly sized ducting or restrictive roof caps Universal Metal Industries Inc disclaims and...

Page 10: ...f restriction anywhere in the ventilation system will cause increased static pressure air resistance that may result in rattling vibration and air buffeting noises as well as inadequate ventilation Se...

Page 11: ...roof cap used needs to be at or above 78 5 square inches See illustrations above Never use a roof cap like the one shown in Figure 1 Instead use a style similar to the one shown in Figure 2 6 Attachi...

Page 12: ...see Drawing B In this example the hood is attached to a built out section of the wall or to a chase It is unlikely that smoke rising past the bottom of the BBQ hood will be captured by the hood Smoke...

Reviews: