Serial Communications 

This series comprises 2 RJ-11-type serial ports and a CANbus port. 
COM1 is RS232 only. COM2 may be set to either RS232 or RS485 via jumper as described below.  

By default, the port is set to RS232. 
Use RS232 to download programs from a PC, and to communicate with serial devices and 

applications, such as SCADA.   
Use RS485 to create a multi-drop network containing up to 32 devices. 

Caution 

 

COM1 & 2 are not isolated 

Pinouts 

To connect a PC to a port that is set to RS485, remove the RS485 connector, and connect the PC 

to the PLC via the programming cable. Note that this is possible only if flow control signals are not 

used (which is the standard case). 

RS232 

 

RS485** 

Controller Port 

Pin # 

Description 

 

Pin # 

Description 

 

Pin #1

 

1* 

DTR signal 

 

A signal (+) 

0V reference 

 

(RS232 signal) 

TXD signal 

 

(RS232 signal) 

RXD signal 

 

(RS232 signal) 

0V reference 

 

(RS232 signal) 

6* 

DSR signal 

 

B signal (-) 

*Standard programming cables do not provide connection points for pins 1 and 6. 

** When a port is adapted to RS485, Pin 1 (DTR) is used for signal A, and Pin 6 (DSR) signal  

     is used for signal B. 

RS232 to RS485: Changing Jumper Settings  

The port is set to RS232 by factory default. 
To change the settings, first remove the Snap-in I/O Module, if one is installed, and then set the 

jumpers according to the following table. 

Note:  

For V230/V280 modules only there is a small window as described on page 5 for jumper 

setting so there is no need to open the controller.

 

 

  Before you begin, touch a grounded object to discharge any electrostatic charge 

  Before removing a Snap-in I/O Module or opening the controller, you must turn off the power 

RS232/RS485 Jumper Settings 
Jumper 

 

RS232*

 

RS485

 

RS485 

Termination

 

*Default factory setting. 

 

 

 

Summary of Contents for Vision 230

Page 1: ...alog weight and temperature measurement I Os via Snap in I O Modules Plug into the back of the controller to provide an on board I O configuration I O Expansion Modules Local or remote I Os may be added via expansion port or CANbus Information Mode This mode enables you to View Edit operand values COM port settings RTC and screen contrast brightness settings Calibrate the touchscreen Stop initiali...

Page 2: ...duct the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repai...

Page 3: ...Installation Guide Unitronics 3 Mounting Dimensions V230 V260 280 290 ...

Page 4: ... The mounting panel cannot be more than 5 mm thick To minimize electromagnetic interference mount the controller on a metal panel and earth the power supply according to the details on page 5 1 Make a panel cut out that suits your model controller V230 Cut out Dimensions V260 280 290 Cut out Dimensions ...

Page 5: ...n the sides of the controller as shown in the figure to the right 5 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 6 When properly mounted the controller is squarely situated in the panel cut out as shown below 5BWiring General This equipment is designed to operate only in SELV PELV Class 2 Limited Power environments All power sup...

Page 6: ...ows Use a metal cabinet Connect the functional earth terminal as described on page 5 Use only the grounding cable provided with the controller Connect the 0V terminal to the earth ground of the system at one point preferably as near to the controller as possible Power Supply The controller requires an external 12 or 24VDC power supply The permissible input voltage range is 10 2 28 8VDC with less t...

Page 7: ...nal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 B signal Standard programming cables do not provide connection points for pins 1 and 6 When a port is adapted to RS485 Pin 1 DTR is used for signal A and Pin 6 DSR signal is used for signal B RS232 to RS485 Changing Jumper Settings The port is set to RS232 by facto...

Page 8: ...ler 2 Open the controller by inserting a flat bladed screwdriver into the slots located on the side of the controller then carefully prying off the rear panel 3 Locate the jumpers and then change the settings as required Settings are shown on page 7 4 Close the controller by snapping the plastic cover back in its place Re installing a Snap in I O Module 1 Line the circular guidelines on the contro...

Page 9: ...the controller Place terminators at each end of the CANbus network Resistance must be set to 1 121Ω 1 4W Connect ground signal to the earth at only one point near the power supply The network power supply need not be at the end of the network CANbus Connector Samara tel 7 846 273 95 85 samara klinkmann spb ru Yekaterinburg tel 7 343 287 19 19 yekaterinburg klinkmann spb ru St Petersburg tel 7 812 ...

Reviews: