2. If you mount the controller on a metal panel, earth the power supply: 

a.  Bore a hole to suit the NC6-32 screw supplied with the kit. 

b.  Scrape panel paint away from the contact area to ensure a conductive 

connection.  

c.  Drive the screw into the hole. 

d.  Place the following hardware screw’s shank, in the order shown in the 

accompanying figure: washer, ring cable shoe, second washer, spring, 

and nut.  

 

  Pay Attention:  

The wire used to earth the power supply must not exceed 10 cm in length 

 if your conditions do not permit this, do not earth the power supply. 

  Make sure that the metal panel is properly earthed. 

  

3. Slide the controller into the cut-out, ensuring 

that the rubber seal is in place. 

 

4. Push the 4 mounting brackets into their slots 

on the sides of the controller as shown in the 

figure to the right. 

5. Tighten the bracket screws against the 

panel. Hold the bracket securely against the 

unit while tightening the screw. 

6. When properly mounted, the controller is squarely situated in the panel cut-out as shown below. 
 

5B

Wiring: General 

 

 

This equipment is designed to operate only in SELV/PELV/Class 2/Limited Power 

environments 

 

All power supplies in the system must include double insulation. Power supply outputs 

must be rated as SELV/PELV/Class 2/Limited Power. 

 

Do not connect either the ‘Neutral or ‘Line’ signal of the 110/220VAC to device’s 0V pin. 

 

Do not touch live wires. 

 

 

All wiring activities should be performed while power is OFF.  

 

Unused pins should not be connected. Ignoring this directive may damage the device 

Caution 

 

To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m 

(5 kgf·cm) 

 

Do not use tin, solder, or any substance on stripped wire that might cause the wire 

strand to break 

 

 

Summary of Contents for Vision 230

Page 1: ...alog weight and temperature measurement I Os via Snap in I O Modules Plug into the back of the controller to provide an on board I O configuration I O Expansion Modules Local or remote I Os may be added via expansion port or CANbus Information Mode This mode enables you to View Edit operand values COM port settings RTC and screen contrast brightness settings Calibrate the touchscreen Stop initiali...

Page 2: ...duct the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repai...

Page 3: ...Installation Guide Unitronics 3 Mounting Dimensions V230 V260 280 290 ...

Page 4: ... The mounting panel cannot be more than 5 mm thick To minimize electromagnetic interference mount the controller on a metal panel and earth the power supply according to the details on page 5 1 Make a panel cut out that suits your model controller V230 Cut out Dimensions V260 280 290 Cut out Dimensions ...

Page 5: ...n the sides of the controller as shown in the figure to the right 5 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 6 When properly mounted the controller is squarely situated in the panel cut out as shown below 5BWiring General This equipment is designed to operate only in SELV PELV Class 2 Limited Power environments All power sup...

Page 6: ...ows Use a metal cabinet Connect the functional earth terminal as described on page 5 Use only the grounding cable provided with the controller Connect the 0V terminal to the earth ground of the system at one point preferably as near to the controller as possible Power Supply The controller requires an external 12 or 24VDC power supply The permissible input voltage range is 10 2 28 8VDC with less t...

Page 7: ...nal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 B signal Standard programming cables do not provide connection points for pins 1 and 6 When a port is adapted to RS485 Pin 1 DTR is used for signal A and Pin 6 DSR signal is used for signal B RS232 to RS485 Changing Jumper Settings The port is set to RS232 by facto...

Page 8: ...ler 2 Open the controller by inserting a flat bladed screwdriver into the slots located on the side of the controller then carefully prying off the rear panel 3 Locate the jumpers and then change the settings as required Settings are shown on page 7 4 Close the controller by snapping the plastic cover back in its place Re installing a Snap in I O Module 1 Line the circular guidelines on the contro...

Page 9: ...the controller Place terminators at each end of the CANbus network Resistance must be set to 1 121Ω 1 4W Connect ground signal to the earth at only one point near the power supply The network power supply need not be at the end of the network CANbus Connector Samara tel 7 846 273 95 85 samara klinkmann spb ru Yekaterinburg tel 7 343 287 19 19 yekaterinburg klinkmann spb ru St Petersburg tel 7 812 ...

Reviews: