Samba™ PLC+ HMI
Unitronics
9
RTD
PT100 (Sensor 0): use Input 9 and 10, related to CM signal.
PT100 (Sensor 1): use Input 7 and 8, related to CM signal.
4 wire PT100 can be used by leaving one of the sensor leads unconnected.
Analog Outputs
Transistor Outputs (pnp)
The 0V signals of the transistor and the analog outputs must be conne
cted to the controller’s 0V.
Outputs 0 to 4 can be used as PWM outputs.
Power Supply
The controller requires an external 24VDC power supply.
The power supply must include double insulation. Outputs must be rated as
SELV/PELV/Class2/Limited Power.
Use separate wires to connect the functional
earth line (pin 3) and the 0V line (pin 2) to the
system earth ground.
Install an external circuit breaker. Guard
against short-circuiting in external wiring.
Double-check all wiring before turning
on the power supply.
Do not connect either the ‘Neutral’ or ‘Line’
signal of the 110/220VAC to device’s 0V pin
In the event of voltage fluctuations or non-
conformity to voltage power supply
specifications, connect the device to
a regulated power supply.