background image

Samba™ OPLC™ 

 

Unitronics 

 

11 

 

 

SM35-J-R20/SM35-J-T20

 

This series comprises a build-in RS232 port.

 

Caution

 

  Signals are related to the controller’s 0V; the same 0V is used by the power supply. 

  The serial port is not isolated. If the controller is used with a non-isolated external device, 

avoid potential voltage that exceeds ± 10V. 

Use RS232 to download programs from a PC, and to communicate with serial devices and 
applications, such as SCADA.  

  

Pinouts 

The pinouts below show the PLC port signals. 

 

RS232 

 

 

 

Pin # 

Description 

 

 

 

 

Not connected 

 

 

 

0V reference 

 

 

 

TXD signal 

 

 

 

RXD signal 

 

 

 

0V reference 

 

 

 

Not connected 

 

 

     

   

Opening the Controller 

 

 

  Before performing these actions, touch a grounded object to discharge any electrostatic charge. 

  Avoid touching the PCB board directly. Hold the PCB board by its connectors. 

     

    

1. Turn off the power supply, disconnects, and dismounts the controller. 
2. The back cover of the controller comprises 4 screws, located in the corners.  

 Remove the screws, and pull off the back cover.                                         

 

Changing I/O Settings 

   The I/O board of the controller is now                      

exposed, enabling you to change  

   I/O settings (module dependent) according to 

the jumpers setting above.  
 
Note: Photo is for illustration purposes only.  
(Using SM70) 

 

 

Closing the Controller 

  Replace the back cover of the controller and fasten the corner screws. 

Note that you must replace the back cover securely before powering up the controller. 

Summary of Contents for Samba OPLC Series

Page 1: ...d on board I Os Item SM35 J R20 SM35 J T20 SM43 J R20 SM43 J T20 SM70 J R20 SM70 J T20 On board I O Model Dependent Screen 3 5 Color Touch 4 3 Color Touch 7 Color Touch Keypad or Function Keys None Programming Com Port Built in RS232 Yes None None USB device mini B None Yes Yes Com Ports separate order user installed The user may install a CANbus module V100 17 CAN and one of the following RS232 R...

Page 2: ...tions Only qualified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas wit...

Page 3: ...Samba OPLC Unitronics 3 Mounting Dimensions SM35 J R20 SM35 J T20 SM43 J R20 SM43 J T20 SM70 J R20 SM70 J T20 ...

Page 4: ...92mm 3 622 x3 622 SM43 122 5x91 5mm 4 82 x3 6 SM70 193x125mm 7 59 x4 92 2 Slide the controller into the cut out ensuring that the rubber seal is in place 3 Push the mounting brackets into their slots on the sides of the panel as shown in the figure below 4 Tighten the bracket s screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted th...

Page 5: ...k Install at maximum distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 3 31 mm 0 13 mm wire 12 16 AWG 1 Strip the wire to a length of 7 0 5mm 0 270 0 300 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure a proper connection 4 Tighten enough to keep the wire from pull...

Page 6: ...ed in a group via a single jumper as either npn or pnp According to jumper settings and appropriate wiring Inputs 10 and 11 can function as either digital or analog inputs Inputs 0 2 and 4 can function as high speed counters as part of a shaft encoder or as normal digital inputs Inputs 1 3 and 5 can function as either counter reset as part of a shaft encoder or as normal digital inputs If inputs 0...

Page 7: ...nk A pnp source B Inputs 10 11 Set as Digital or Analog Set to JP5 Input 10 JP6 Input 11 Digital A A Analog B B Analog Inputs AN0 AN1 Set Type Set to JP3 AN0 JP4 AN1 Voltage A A Current B B Default settings I O Wiring npn Input Wiring SM35 43 70 J R20 SM35 43 70 J T20 Input wiring npn sink HSC input wiring npn sink ...

Page 8: ...Samba OPLC Installation Guide 8 Unitronics pnp Input Wiring SM35 43 70 J R20 SM35 43 70 J T20 Input wiring pnp source HSC input wiring pnp source Shaft encoder SM35 43 70 J R20 SM35 43 70 J T20 ...

Page 9: ...l of the analog input must be connected to the controller s 0V Relay Outputs Transistor Outputs SM35 43 70 J R20 SM35 43 70 J T20 Increasing Contact Life Span SM35 43 70 J R20 Only To increase the life span of the relay output contacts and protect the device from potential damage by reverse EMF connect A clamping diode in parallel with each inductive DC load An RC snubber circuit in parallel with ...

Page 10: ...s 0V pin 6 In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Earthing the OPLC To maximize system performance avoid electromagnetic interference by Mounting the controller on a metal panel Connect each common and ground connection directly to the earth ground of your system For ground wiring use the shortest...

Page 11: ...nected Opening the Controller Before performing these actions touch a grounded object to discharge any electrostatic charge Avoid touching the PCB board directly Hold the PCB board by its connectors 1 Turn off the power supply disconnects and dismounts the controller 2 The back cover of the controller comprises 4 screws located in the corners Remove the screws and pull off the back cover Changing ...

Page 12: ... www klinkmann by RUSSIA klinkmann klinkmann ru www klinkmann ru LATVIA info klinkmann lv www klinkmann lv LITHUANIA info klinkmann lt www klinkmann lt ESTONIA info klinkmann ee www klinkmann ee UKRAINE klinkmann klinkmann kiev ua www klinkmann com ua KAZAKHSTAN klinkmann klinkmann kz www klinkmann kz ...

Reviews: