7 Faults
Q3 1000-2000A
29
Error diagnosis
Malfunction
Causes
Motor does not run
-
Wrong power supply and motor connections
- Activated fuses
- Missing enable or command value
- Current limit too low
- Missing BTB
Motor speeds up
- Wrong polarity of the actual value
(tacho
armature voltage)
- Values of the tacho switch S9 too low
- Command value too high
For armature voltage control
- Field current too low
- Fuses, armature voltage feedback activated
Motor runs unsteadily
- Mechanical defect of the tacho
- Tacho malfunction
- Amplification of the speed controller too low
or too high
- Wrong PID parameter
- Command value errors
- Amplification of the current controller too
low or too high
No motor torque
- Current limits too low
- Field current too low
- Mechanical overload of the axis
E
rr
o
r
d
ia
g
no
si
s