5500 Moisture Detection Series Installation Instructions 

Dimensions 

Figure 2: Dimensions 

 

Specifications 

Loop type 

Closed 

Battery type 

Lithium 

Battery life 

Approximately 10 to 15 years 

Alarm response 

10 seconds delay, then on as long as wet 

Test button 

Simulates moisture for test 

LED 

Flashes every 2 seconds on alarm 

Trigger response 

500 K ohm 

Sensor isolation from 
ground 

Photo coupled 

Sensing circuit 

AC to eliminate electrolysis (1 Hz) 

Cable Length 

100 ft. (30 m) maximum 

Loop resistance 

10 ohms maximum (nonalarm) 

1 M ohm minimum (alarm) 

Operating temperature 

     5501 processor 

     5515 sensors 

 

0 to 125°F (-17 to 51°C) 

33 to 180°F (0 to 82°C) 

Number of sensors per 
processor 

4 maximum 

 

Ordering information 

Model #  Description 

Loop type 

Color 

Lead 

5501 

Moisture 
processor 

Closed 

Mahogany 
brown 

Terminals 

5515 

Surface-
mount sensor 

NA 

Gray 

10 ft. (3 m) 

Regulatory information 

Manufacturer 

PLACED ON THE MARKET BY: 
UTC Fire & Security Americas Corporation, Inc. 
3211 Progress Drive, Lincolnton, NC, 28092, 
USA 

AUTHORIZED EU REPRESENTATIVE: 
UTC Fire & Security B.V. 
Kelvinstraat 7, 6003 DH Weert, Netherlands 

Product warnings 
and disclaimers 

 

THESE PRODUCTS ARE INTENDED FOR 
SALE TO AND INSTALLATION BY QUALIFIED 
PROFESSIONALS. UTC FIRE & SECURITY 
CANNOT PROVIDE ANY ASSURANCE THAT 
ANY PERSON OR ENTITY BUYING ITS 
PRODUCTS, INCLUDING ANY “AUTHORIZED 
DEALER” OR “AUTHORIZED RESELLER”, IS 
PROPERLY TRAINED OR EXPERIENCED TO 
CORRECTLY INSTALL FIRE AND SECURITY 
RELATED PRODUCTS. 

For more information on warranty disclaimers and 
product safety information, please check 

https://firesecurityproducts.com/policy/product-
warning/

 or scan the QR code. 

Contact information 

www.utcfireandsecurity.com

 or 

www.interlogix.com

 

For customer support, see 

www.interlogix.com/customer-

support

  

 

Reviews: