4.5 Read-only parameters menu
No.
Description
Unit
Min.
Max.
By default
Increment
Possible choices
Visibility
Levels
P250
Aérotherm sensor temperature
°C
-
-
-
-
-
-
1
P251
42AMA sensor temperature
°C
-
-
-
-
-
If 42AMA
present = YES
1
P255
Aérotherm fan speed
%
-
-
-
-
-
-
1
P256
42AMA fan speed
%
-
-
-
-
-
If 42AMA
present = YES
1
P257
Valve opening
%
-
-
-
-
-
-
1
P260
Fresh air damper state
C - O
-
-
-
-
Open/Closed
If fresh air damper
present = YES
1
P261
Changeover contact state
C - O
-
-
-
-
Open/Closed
If coil type
= mixed
1
P262
Fan operation feedback state
C - O
-
-
-
-
Open/Closed
-
1
P263
Antifreeze thermostat state
C - O
-
-
-
-
Open/Closed
If frost protection
thermostat present
= YES
1
P264
Remote on/off command state
C - O
-
-
-
-
Open/Closed
-
1
P265
42AMA operation feedback
state
C O
-
-
-
-
-
If 42AMA
present = YES
1
P270
42AMA calculated ∆t
°C
-
-
-
-
-
If 42AMA
present = YES
1
4.6 Versions Menu
U :01 PROGRAM pr1
42AM Control
V 03.00 11/07/16
Bios: 06.42
Boot: 04.05
Shows the name and version of the program installed on the microprocessor.