6

-

VENTING REQUIREMENTS

•  INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.

• 

DO NOT CONNECT THE PELLET VENT TO A VENT SERVING ANY OTHER APPLIANCE OR STOVE.

• 

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.

The following installation guidelines must be followed to ensure conformity with both the safety listing of this stove 

and to local building codes. Do not use makeshift methods or compromise in the installation.

MAXIMUM VENTING DISTANCE

Installation MUST include at least 3-feet of vertical pipe outside the home. This will create some natural draft to 

reduce the possibility of smoke or odor during appliance shutdown and keep exhaust from causing a nuisance 

or hazard by exposing people or shrubs to high temperatures. The maximum recommend vertical venting height 

is 12-feet for 3-inch type “PL” vent. Total length of horizontal vent must not exceed 4-feet. This could cause back 

pressure. Use no more than 180 degrees of elbows (two 90-degree elbows, or two 45-degree and one 90-degree 

elbow, etc.) to maintain adequate draft.

IMPORTANCE OF PROPER DRAFT

Draft is the force which moves air from the appliance up through the chimney. The amount of draft in your 

chimney depends on the length of the chimney, local geography, nearby obstructions and other factors. Too 

much draft may cause excessive temperatures in the appliance. Inadequate draft may cause backpuffing into 

the room and ‘plugging’ of the chimney.

Inadequate draft will cause the appliance to leak smoke into the room through appliance and chimney 

connector joints.

An uncontrollable burn or excessive temperature indicates excessive draft.

Take into account the chimney’s location to ensure it is not too close to neighbors or in a valley which may 

cause unhealthy or nuisance conditions.

PELLET VENT TYPE

A UL listed 3-inch or 4-inch type “PL” pellet vent exhaust system must be used for installation and attached to the 

pipe connector provided on the back of the stove (use a 3-inch to 4-inch adapter for 4-inch pipe). Connection 

at back of stove must be sealed using Hi-Temp RTV. Use 4-inch vent if the vent height is over 12-feet or if the 

installation is over 2,500 feet above sea level.

We recommend the use of Simpson Dura-Vent® or Metal-Fab® pipe (if you use other pipe, consult your local 

building codes and/or building inspectors). Do not use Type-B Gas Vent pipe or galvanized pipe with this unit. The 

pellet vent pipe is designed to disassemble for cleaning and should be checked several times during the burning 

season. Pellet vent pipe is not furnished with the unit and must be purchased separately.

PELLET VENT INSTALLATION

The installation must include a clean-out tee to enable collection of fly ash and to permit periodic cleaning of the 

exhaust system. 90-degree elbows accumulate fly ash and soot thereby reducing exhaust flow and performance 

of the stove. Each elbow or tee reduces draft potential by 30% to 50%.

All joints in the vent system must be fastened by at least 3 screws, and all joints must be sealed with Hi-Temp 

RTV silicone sealant to be airtight. The area where the vent pipe penetrates to the exterior of the home must be 

sealed with silicone or other means to maintain the vapor barrier between the exterior and the interior of the 

home.

Vent surfaces can get hot enough to cause burns if touched by children. Noncombustible shielding or guards 

may be required.

PELLET VENT TERMINATION

Do not terminate the vent in an enclosed or semi-enclosed area, such as; carport, garage, attic, crawl space, 

under a sun deck or porch, narrow walkway, or any other location that can build up a concentration of fumes. 

The termination must exhaust above the outside air inlet elevation. The termination must not be located where it 

will become plugged by snow or other materials. Do not terminate the venting into an existing steel or masonry 

chimney.

IMPORTANT! This unit is equipped with a negative draft system that pulls air through the burn pot and pushes 

the exhaust out of the dwelling. If this unit is connected to a flue system other than the way explained in this 

manual, it will not function properly.

Summary of Contents for KP130

Page 1: ...he appliance Keep viewing and ash removal doors tightly closed during operation Replace glass with 5mm ceramic glass ONLY IMPORTANT When the hopper lid is open the auger will stop Close the hopper lid...

Page 2: ......

Page 3: ...R FUTURE REFERENCE Please read this entire manual before installation and use of this appliance Failure to follow these instructions could result in property damage bodily injury or even death Contact...

Page 4: ...ced on a non combustible surface or on the ground well away from all combustible materials pending final disposal The exhaust system should be checked monthly during the burning season for any build u...

Page 5: ...Environmental Protection Agency s crib wood emission limits for wood heaters sold after May 15 2020 Under specific EPA test conditions burning wood pellet fuel this heater has been shown to deliver he...

Page 6: ...an NFI certified specialist IMPROPER INSTALLATION The manufacturer will not be held responsible for damage caused by the malfunction of a stove due to improper venting or installation Call 800 750 272...

Page 7: ...m CORNER D Adjacent wall to unit 8 00 203mm ALCOVE E Alcove depth 36 00 914mm 5500 M only F Alcove height 60 00 520mm CLEARANCES Your pellet stove has been tested and listed for installation in reside...

Page 8: ...the stove use a 3 inch to 4 inch adapter for 4 inch pipe Connection at back of stove must be sealed using Hi Temp RTV Use 4 inch vent if the vent height is over 12 feet or if the installation is over...

Page 9: ...ction of pipe should be added with a horizontal cap which would complete the installation see FIGURE 7 A support bracket should be placed just below the termination cap or one every 4ft 1 22m to make...

Page 10: ...ection to the heater SPECIAL MOBILE HOME REQUIREMENTS WARNING Do not install in a sleeping room CAUTION The structural integrity of the mobile home floor wall and ceiling roof must be maintained A wor...

Page 11: ...a forced draft pressure is required for the combustion process inside your stove it is extremely important that the exhaust system be properly installed and maintained And that when operating your st...

Page 12: ...at will not properly control the unit When adjusting the Draft Fan setting try only 1 setting above or below the heat setting It is better to leave the stove in the automatic mode ROOM FAN The room fa...

Page 13: ...the preselected desired heat range setting 1 to 5 and the minimum heat range setting of 1 The T Stat will not turn the stove on and off When the desired room temperature has been reached and the T Sta...

Page 14: ...w LEDs will be off 5 Hopper Switch Test The display will show hppr The ON LED is lit If the hopper switch is open lid is open the HEAT RANGE LED will turn on If the lid is closed the HEAT RANGE LED wi...

Page 15: ...the heat exchanger in the stove reaches the factory preset temperature Attempts to achieve heat output rates that exceed heater design specifications can result in permanent damage to the heater First...

Page 16: ...ck panel or opening the exhaust system for any inspection cleaning or maintenance work Never perform any inspections cleaning or maintenance on a hot stove Do not operate stove with broken glass leaka...

Page 17: ...We recommend using a high quality glass cleaner Should a build up of creosote or carbon accumulate you may wish to use 000 steel wool and water to clean the glass DO NOT use abrasive cleaners DO NOT p...

Page 18: ...re that the viewing door is closed and sealed properly If not adjust door catch and or replace door gaskets Check that all outside connections are clear of any obstructions Check the exhaust system cl...

Page 19: ...tor This indicates that the stove is in normal operation and is running in the automatic mode However either the draft fan or room fan setting is manually configured Flashing Draft Fan Setting Indicat...

Page 20: ...18 GRAY BLACK Wiring Diagram CORRECT WRONG Ensure the wires are connected to the bottom two prongs of the hopper switch as shown...

Page 21: ...ght 1 12 69787 Hopper Assembly 1 13 80491 MIcroswitch 1 14 83541 4 40 Bolt 2 15 893039 Remote Sensor Bracket 1 16 25480MB Access Panel 1 17 80461 Power Supply Cord 1 18 80462 Receptacle 3 Prong 1 19 8...

Page 22: ...20 9 3 2 1 5 6 4 7 8 10 Parts Diagram 47 46 48 49 50...

Page 23: ...07 Date _____________________ Engineer Name ________________________________ License No ____________________________________ Company _____________________________________ Telephone No _______________...

Page 24: ...s pi ces d tach es Gardez ce manuel dans un lieu s r pour toute consultation ult rieure Lorsque vous nous crivez donnez toujours le num ro de mod le complet qui se trouve sur la plaque signal tique fi...

Page 25: ...____________________________ Service de 07 Date _____________________ Nom de l ing nieur ____________________________ N de licence _________________________________ Compagnie _________________________...

Page 26: ...e Droit 1 12 69787 Assembl e Hopper 1 13 80491 Micro Interrupteur 1 14 83541 4 40 Bolt 2 15 893039 Support de capteur distance 1 16 25480MB Panneau D acc s 1 17 80461 Cordon D alimentation 1 18 80462...

Page 27: ...20 Sch ma des pi ces 9 3 2 1 5 6 4 7 8 10 47 46 48 49 50...

Page 28: ...SOSTAT MARRON MARRON NOIR BLANC ROUGE BLEU ORANGE PRISE MOLEX AU CIRCUIT IMPRIM PCB PRINCIPAL NOIR NOIR NOIR BLANC BLANC SOUFFLANTE DE DISTRIBUTION VENTILATEUR D VACUATION THERMISTOR Sch ma de c blage...

Page 29: ...eux fois par seconde Cela indique que le po le fonctionne normalement et qu une condition de temp rature excessive existe provoquant l arr t du combustible Indicateur de r glage du niveau de chaleur H...

Page 30: ...e V rifiez que le raccordement du pressostat au foyer ne contienne aucune cendre ni obstruction Le syst me vis sans fin est bloqu ou il y a une vo te de combustible dans la tr mie qui emp che le combu...

Page 31: ...le et d paisseur correctes doivent tre utilis es NE substituez PAS le verre avec des mat riaux alternatifs Contactez votre revendeur autoris pour obtenir ce verre R installez le nouveau verre en le fi...

Page 32: ...fi peut effectuer ces travaux Il est aussi recommand qu avant chaque saison de chauffage le syst me complet soit inspect nettoy et si n cessaire r par par un professionnel Pour nettoyer la chemin e d...

Page 33: ...sur le bouton OFF arr t et ensuite de nouveau sur le bouton ON marche pour commencer une nouvelle s quence de mise en route 2 Si le po le a refroidi il se r initialisera l tat OFF arr t ce moment l vo...

Page 34: ...de l eau sal e 11 Bois non s ch ou 12 Produits du papier carton contreplaqu ou panneau de particules L interdiction de br lage de ces mat riaux n interdit pas l utilisation d allume feu compos s de pa...

Page 35: ...fin se met en marche plein r gime Si le fusible de la vis sans fin n a pas saut et que le circuit de d tection fusible fonctionne le voyant DEL Heat Range du degr de chaleur sera allum et les trois au...

Page 36: ...justez le r glage du ventilateur de tirage essayez seulement 1 r glage au dessus ou en dessous du r glage de chaleur Il est pr f rable de laisser le po le en mode automatique VENTILATEUR DE LA PI CE L...

Page 37: ...rage forc e est n cessaire au processus de combustion l int rieur de votre po le il est extr mement important que le syst me d vacuation soit install correctement et maintenu Et que lors du fonctionne...

Page 38: ...ionn de la plage de chaleur d sir e 1 5 et le r glage de la plage de chaleur minimale de 1 Le T Stat n allumera ni ne teindra le po le Lorsque la temp rature ambiante souhait e est atteinte et que le...

Page 39: ...nag e Apr s le d m nagement tous les vents doivent tre r install s et fix s fermement L air ext rieur est obligatoire pour l installation d une maison mobile Consultez votre revendeur lors de l achat...

Page 40: ...rd en T de regard devra tre plac sur le tuyau avec une sortie 90 degr s hors de la maison ce point une partie de tuyau de 3 pieds 0 91m minimum devra tre ajout e avec un couvercle horizontal qui devra...

Page 41: ...e doit tre scell en utilisant un produit vulcanis RTV pour temp ratures lev es Utilisez une ventilation de 4 pouces si la hauteur de ventilation est sup rieure 12 pieds ou si l installation se trouve...

Page 42: ...re minimum plus grand afin d obtenir un acc s commode au panneau de contr le FIGURE 3 D GAGEMENTS DE LA PAROI LAT RALE INSTALLATION EN PARALL LE FIGURE 4 D GAGEMENTS DE LA PAROI LAT RALE INSTALLATION...

Page 43: ...cialiste certifi NFI NE CONNECTEZ PAS CETTE UNIT UN CONDUIT OU CIRCUIT DE DISTRIBUTION D AIR INSTALLATION INCORRECTE Le fabricant ne sera pas tenu responsable des dommages caus s par un dysfonctionnem...

Page 44: ...vos pellets dans un endroit sec NE stockez PAS le carburant dans les d gagements d installation de l appareil ou dans l espace requis pour faire le plein et enlever les cendres Cela pourrait provoque...

Page 45: ...oivent tre jet es dans un conteneur m tallique avec un couvercle d ajustement serr Le conteneur ferm dans lequel se trouvent les cendres devra tre plac sur une surface non combustible ou sur le sol bi...

Page 46: ...reil n est pas destin tre utilis en tant que principale source de chaleur U S Environmental Protection Agency Certifi aux normes d missions de 2020 particules CONSERVEZ CES INSTRUCTIONS CE MANUEL VOUS...

Reviews: