-5-
CLEARANCES TO COMBUSTIBLES
It is of utmost importance that the clearances to combustible materials be strictly adhered to during installation
of the stove. Refer to the tables below.
•
If there is a Horizontal run of flue pipe there must be at lease 18” of clearance between the pipe and the
ceiling. There also has to be floor protection under the horizontal run that extends 2” beyond each side of the
flue pipe.
•
Floor to ceiling height must be at least 7’ (2.13m) in all cases.
•
Do not place any combustible material within 4’ (1.2m) of the front of the unit.
•
The clearance between the flue pipe and a wall are valid only for vertical walls and for vertical flue pipe.
•
The chimney connector must not pass through an attic or roof space, closet or similar concealed space, a
floor, or a ceiling.
•
For Canadian installations, where passage through a wall, or partition of combustible construction is desired,
the installation must conform to CAN/CSA-B365.
•
A flue pipe crossing a combustible wall must have a minimum clearance of 18” (457.2mm).
•
To reduce flue clearances from combustible materials, contact your local safety department.
Single Wall Pipe
(Double Wall Pipe)
Key
in
mm
A
15 (12) 381 (305)
B
18 (18) 458 (458)
C
19 (16) 483 (407)
D
29 (29) 737 (737)
E
12 (12) 305 (305)
F
22 (22) 559 (559)
D
B
A
C
E
F
E
D
B
A
C
E
F
E