Specification
The technical specifications for the MUX-414 are listed in
, and
technical specifications for the MUX-418 are listed in
Table 1-2. DNx-MUX-414 Technical Specifications
p
Output confi guration
14 independent 1 x 3 switches
Output specifi cations
Rated Load (continuous) 1 A (-40 to +85°C) 2 A (-40 to +25°C)
Rated Load (peak)
3 A < 0.1 second
Max Operating Voltage
48 VDC, 48 V peak in AC waveforms,
34 Vrms (sinusoidal signals)
Absolute Max Voltage
55 VDC
Contact type
Solid State
Contact ON impedance
0.2 Ohm typical, 0.25 Ohm max (at the I/O
connector)
Contact OFF impedance
>100 MOhm
Off Leakage Current
< 5 nA typical, <3 μA max over full temp range
Max update rate
250 Hz (including break-before-make timing)
Turn-Off Time
<0.2 mS typical (1 mS max)
Turn-On Time
< 0.45 mS typical (2 mS max)
Power up / reboot state
All Switches Off
Sync in/out specifi cations
Sync in High Voltage
2.8 V min
Sync in Low Voltage
1.0 V max
Sync out High Voltage
3.55 V min / 4.0 V max @ 3 mA
Sync out Low Voltage
0.4 V max @ 3 mA
Power dissipation
< 5 W
Isolation
350 Vrms
Isolation resistance
>1 GOhm
Operating Temp. Range
Tested -40 to +85 °C
Operating Humidity
95%, non-condensing
Vibration
IEC 60068-2-6
IEC 60068-2-64
5 g, 10-500 Hz, sinusoidal
5 g (rms), 10-500 Hz, broad-band random
Shock
IEC 60068-2-27
50 g, 3 ms half sine, 18 shocks @ 6 orientations
30 g, 11 ms half sine, 18 shocks @ 6 orientations